Flash Technology
Revision A - 2/13/2020
60
TARGET A2D VALUES
Operating
Mode
Low Temp.
-40C/-40F
String Voltage
Target
High Temp.
55C/131F
String Current
Target
String Voltage Drop if 1
LED is lost
White Day
+50
950
-50
920
40
White Twi
+60
820
-60
300
34
White Night
+30
570
-30
570
24
Red Night
+45
755
-45
565
50
IR Night
+20
565
-20
NA
38
Low Temp,
Higher SV
Based at
24C/75F
Ambient
Higher Temp,
Lower SV
+ / - 10%
FINDING THE A2D VALUES:
The following steps will be used to navigate to the A2D values within the system controller while onsite.
1.
Press the ENTER button (1) time.
2.
Scroll down to “Local Diagnostics” using the ↓ arrow and press ENTER.
3.
Scroll down to HI Beacon Tier (or BCN depending on the FW version) and press ENTER.
4.
Scroll down to Tier BCN press Enter
5.
Select proper A2D (White, Red, IR) press Enter.
6.
Select panel 1-3 press Enter
7.
Select string View Voltage and Current Values