Complete the following steps before applying power:
Examine installation drawings.
Ensure the unit is wired according to the included instructions.
Check all terminal strip connections for tightness.
If external alarm detection circuit responds to closed contacts, ensure they are wired to the proper
contacts that close on alarm.
If external alarm detection circuit responds to open contacts, ensure they are wired to the proper
contacts that open on alarm.
Verify alarm wiring has been protected by using shielded wires. Also verify proper grounding of the
shield wire, and that the wires are run through conduit.