6. Assembly
6.1 Setup
A/B
C (Flamcomat starter)
•
Fit the automatic vent (supplied separately).
•
Remove the transport seal by the volume sensor once the basic vessel has been set up in the proposed place and no further
positional changes are necessary. Avoid impact on the sensor and make sure the sensor is on a surface which does not impair
the function of the sensor pressure-pad.
•
Installation of the weight-capacity sensor and the adjustable feet.
•
Using the foot-height adjuster, adjust the vessel until it is vertical. Use two vertical magnetic spirit levels.
•
Ensure that no external additional forces can be exerted on the basic vessel (e.g. tools laid on the vessel, things leaning on the
sides).
•
Do not fix the basic vessel to the ground on which it is erected (do not use any sort of fastening which can adversely affect the
vessel, e.g. sinking the feet into concrete or lime, welding of the vessel or its feet, clamps and ties on the body of the structure
or appurtenances).
•
Place the control module, the basic vessel and the auxiliary vessel at the same height.
6.2 Vessel connection
The vessel connection is produced as an electric or hydraulic connection to the pump module. For the installation diagram
and example installation see appendix 1. Please observe the following points prior to filling and commissioning of the pressure
expansion vessels:
•
Install the connection assembly between the vessel and the control module.
Caution:
Ensure that the connection between the pump module and the basic vessel is made with the supplied flexible pressure
hoses (connection assembly).
Fig. FM.030.V01.15
1000 Ltr
1000 Ltr
≤
>
Fig. FM.031.V01.15
Fig. FM.032.V01.15
Fig. FM.033.V01.15