Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value
Error message
number
8-4- 1
Pressure
OFF
Minimum operating pressure ON (actual pressure):
Default setting has been reached or not achieved; lockshield
valves in vessel or return connection in incorrect position,
insufficient capacity of pumps, improper system layout, or as
consequence of error no.: 10-16;
15-17; 19; 20; 22-27 /, check system lay-out, electronic
installation, pumps, leak-tightness of the equipment and system
and lockshield valves; insufficient capacity diagnosed » service;
Error OFF: self-resetting when error resolved.
P
A
- P
A-
– 0.3 bar
8
Maximum operating pressure ON (actual pressure):
Default setting has been reached or exceeded; lockshield valves
in return connection in incorrect position, improper system
layout, or as consequence of error no. : 11; 20 / check system
lay-out, electronic installation, valve 1; 2 , particle filter, return
connection, lockshield valve;
if necessary » service; Error OFF: self-resetting when error
resolved.
P
A
+ P
A+
+ 0.3 bar
9
8-4- 2
Level vessel
OFF
Minimum fill level vessel ON:
Default setting has been reached or not achieved; pump motor
1; 2 is turned off; with top-up feature installed, top-up is ON
(rising level starting at 0%); see error no.: Error OFF: self-
resetting when error resolved.
5 %
10
Minimum priming water ON:
Default setting has been reached or not achieved; pump motor
1; 2 is turned OFF, no pressure increase; may be followed by
error no.: 8; execution without top-up feature, insufficient initial
filling or as consequence of error no.: 22-27 / check top-up
functioning, leaks in equipment, system lay-out; if necessary
re-fill manually, beware of error no: 11! Error OFF: self-resetting
when error resolved.
6 %
19
Maximum fill level vessel ON:
Default setting has been reached or exceeded;
Valves 1; 2 (3 is OFF) are switched OFF, pump motor 1;
2 are not switched ON; no pressure increase or decrease;
following error may be error no.:(8) 9; improper system lay-out
of initial filling / check functioning of valves 1; 2; 3; check check
valves, expansion volume, drain system water (beware of error
no.: 19); Error OFF, when error is resolved and reset.
A, B vessel: 96%
C vessel: 81%
11
8-4- 3
Diaphragm rupture (optional)
OFF
Diaphragm rupture sensor ON:
Water at the electrodes of the conductive sensor; pump motors
1; 2 and 1; 2; 3 valves are turned off, no pressure increase,
reduction and top-up;
may be followed by error no.: 8; 9; probably diaphragm
rupture/open condensate drain. If the opening results in water
discharging continuously, the diaphragm should be visually
checked for ruptures and leaks (note: inspect the vessel
internally, which is part of the routine vessel inspection), clean
the inside of the vessel, if necessary service; Error OFF, when
error is resolved and reset.
20
8-4- 4
Level top-up pump (optional)
OFF
Minimum fill level top-up pump ON:
Insufficient level in break tank of top-up unit;
top-up pump is turned off, no top-up function,
feed pressure is too low, feed-valve with insufficient flow rate,
may be followed by error-no.: 8; 10; 19 /
check feed conditions; Error OFF, self-resetting when error is
resolved.