4.5 Appropriate use
Sealed water-based heating and cooling systems in which temperature-induced changes in the volume of the system water (the
heat transfering agent) can be absorbed and the required operating pressure is governed by a separate expansion automat.
The water-based heating systems are subject to EN 12828. For temperatures above 105 °C or system capacities over 1 MW,
additional rules and regulations may apply. The Principal / Operator will need to consult with a notified body on additional safety
measures.
Use in similar systems (e.g. heat transfer systems for process industry or technologically conditioned heat) may require special
measures. Please note that the Flamcomat Starter must not be used in systems with mostly stainless steel piping and not in
combination with a vacuum degasser. The complementary documents must be studied.
4.6 Incoming goods
The items delivered must be compared against the items listed on the shipping note and inspected for conformity. Unpacking,
installation and commissioning may be started only once the product has been checked to conform with the intended use as
stated in the order process and contract. In particular, exceeding the permissible operating or design parameters may lead to
malfunctioning, component damage and personal injury.
If not in line with conformity or if the delivery is incorrect in another way, the product must not be used.
4.7 Transportation, storage, unpacking
The equipment is delivered in packaging units in accordance with the contract specifications or the specifications required for
certain modes of transport and climate zones. These units meet at least the requirements set out in the Flamco B.V. packaging
directives. In accordance with these directives, expansion vessels must be transported horizontally and pump units upright; each
packaged on throw-away pallets. If the packaging is suitable for use with hoisting gear, this will be indicated at the designated
hoisting points.
Important note:
Transport the packed goods as close as possible to the envisaged set-up location and make sure there is a
horizontal, solid surface on which the goods can stand.
Note!
Take all necessary precautions to ensure that the expansion vessel cannot topple over or wobble once it has been
unpacked and removed from the pallet.
Suitable lifting lugs are provided for lifting and moving suspended empty vessels prior to installation. Such devices (lifting lugs)
must be used in tandem; avoid side-pulling.
Once it has been removed from the pallet and the packaging, the unit must be transferred by pulling it over suitable surfaces. Use
methods that prevent uncontrolled falling, sliding or tipping over. The lifting lugs on the pump unit are designed so the unit can be
lifted vertically. They may not be subjected to any lateral force.
The goods may also be warehoused in their packaging. Once it has been removed from its packaging, the equipment must be
put in position, observing standard safety procedures. Do not stack the equipment.
Use only permitted lifting gear and safe tools and wear the required personal protective equipment.
4.8 Operations room
Definition: room which meets the applicable European regulations, European and harmonised standards and relevant technical
rules and guidelines of the professional associations for this field of application. For the use of the expansion automat as
prescribed in this manual these rooms generally contain equipment for thermal generation and distribution, water heating/cooling
and top-up, power source and distribution, such as measuring, control engineering, control technology and IT.
Access for unqualified and untrained persons must be restricted or forbidden.
The set-up location of the expansion automat must ensure that operation, service, maintenance, inspection, repair, installation
and dismantling can be carried out unhindered and without danger. The floor of the set-up location for the expansion automat
must be such that stability is guaranteed and maintained. Bear in mind that the maximum possible forces can be exerted from the
net mass including the water volume. If stability cannot be guaranteed, there is a danger that the vessel will tip over or move and,
as a consequence in addition to functional defects may lead to personal injury.
The ambient atmosphere must be free from conductive gases, high concentrations of dust and aggressive vapours. There is the
risk of explosion if any combustible gases are present.