TemplateA4_v20130506
33
Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value
Error message
number
8-4- 9
Top-up (optional)
OFF
Top-up water volume too low (pulse water meter, option).
No impulse from impulse water meter after top-up
request; valve 3, motor 3 are switched OFF,
feed pressure too low, valve in incorrect position
or not functioning properly, motor 3 with insufficient
or no pump capacity; exception: Signal line
is not installed or is missing, water meters without function /
check electrical installation, check component functions, ensure
feed
conditions;
Error OFF off after, when error is resolved and reset.
22
Top-up without request (impulse water meter, option)
Impulse received from impulse water meter without request for
top-up, valve 3, motor 3 are switched OFF; equipment in flow
direction after the water meter or valve 3 is leaking or fails to
close (incorrect flow direction due to check valve blocking) /
check functioning and check for leaks in the equipment;
Error OFF off after, when error is resolved and reset.
23
Minimum cycle distance exceeded
24
Maximum no. of cycles per timeframe exceeded
25
Maximum top-up cycle amount exceeded
(impulse water meter, optional)
26
Maximum top-up cycle time exceeded
27
8-4- 10
Overflow spill (optional)
OFF
Draining amount too low (impulse water meter, optional). No
impulse from impulse water meter after draining request; valve
3.1, motor 3.1 are switched OFF, feed pressure too low, valve
in incorrect position or not functioning properly, motor 3.1 with
insufficient or defective pump capacity; Exception: Signal line is
not installed or is missing, water meter without function/check
electrical installation, check component function, ensure feed
conditions;
Error OFF off after, when error is resolved and reset.
28
Drainage without request (impulse water meter, option)
Impulse received from impulse water meter without request for
drainage, valve 3.1, motor 3.1 are switched OFF;
equipment in in flow direction downstream of the water meter
or
valve 3.1 is leaking or fails to close (incorrect flow direction due
to check valve
blocking) / check functioning and
check for leaks in the equipment;
Error OFF off after, when error is resolved and reset.
29
8-4- 11
Treatment (optional)
OFF
First message (warning), 70% of the treatment volume entered
in the menu has been reached.
Prepare replacement module! Reset error message.
70%
55
Second message (warning), 90% of the treatment volume
entered in the menu has been reached. This message replaces
the first message , if no. 55 has not been reset. The value on the
display is inverted and flashes. Prepare replacement module!
(if necessary, replace module, observe error message no.: 31)
90%
61
Third message (warning), 100% of the treatment volume entered
in the menu has been reached. This message replaces the first
message , if no. 61 has not been reset. The value on the display
is inverted; top-up is interrupted.
May be followed by error no. 19. To maintain
the pressure (pressure increase), replace the module,
reset the value, and then, if necessary, modify the entry for
possible treatment volume, see page 32.
100%
31
ENG