Technical Description
Multi
-DENCO
30
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
Running redundancy
Instead of the standby unit(s) remaining off, running redundancy allows all units to ope-
rate at the same time, reducing their cooling requirements. This is can be referred to
as 'Hot/Cold Standby'.
Each unit will operate on 'part load', reducing the speed of the fans and other variable
components. The network would still have backup capability: if a unit developed a fault
the other units would use their spare capacity to meet the cooling requirements.
By operating in part load, there are significant energy savings when compared to a tra-
ditional 'Duty/Standby' operation. The diagram shows an example of savings available:
Fig. 3-2:
Running Redundancy Example
Sensor averaging
Sensor averaging can be calculated on temperature, humidity or both, when
Multi
-DENCO units are connected in a network. Each unit sends their sensor readings
to every unit in the network. Each unit then takes all the values and calculates the aver-
age independent of the network units.
This gives the advantage of balancing the cooling requirements across all of the units
within a room, rather than on individual airflows. The software has features to allow for
sensor, communication or unit failure, so that the values do no distort the average
value and the unit can change back to 'stand-alone' if necessary.
Automatic Pressurisation
System (APS)
APS ensures a constant pressure in the floor plenum by the
Multi
-DENCO unit. This
can help reduce hot spots and allows for fast reaction to changes in airflow.
This also saves energy as the
Multi
-DENCO fans only supply the same amount of air
to the floor void, as the amount of air being removed by servers.
For datacentres, this feature can be especially efficient when combined with cold-aisle
containment.
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...