Servicing and Maintenance
Multi
-DENCO
102
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
10.7 Logbook & EU Regulation
A logbook should be available throughout the working life of the equipment. In the EU
this is a legal requirement if the system charge is 2.3 kg or above.
The logbook needs to be updated after each maintenance to comply with
EN 378-4:2008+A1:2012 and should include the following information:
– Initial refrigerant charge following commissioning
– Details of any maintenance or repair work
– Quantities of new, re-used or recycled refrigerant additions or removals
– If there is details of re-used refrigerant, the results should be kept in the
logbook also
– The refrigerant source should also be recorded
– Changes and replacements of any components of the refrigeration system
– Results of all periodic, routine tests
– The periods of any significant non-use
Members of the EU must also comply with the Fluorinated Greenhouse Gases Regu-
lation (EU) No 517/2014, alongside any further country specific legislation. This regu-
lation places responsibility for record keeping and leak detection on the owner/operator
of the equipment and the company that services it.
Information required for this regulation is more comprehensive than a simple logbook
and a required period for record keeping, therefore all parties involved should have an
understanding of the regulations implications. Furthermore, individual countries can
impose stricter rules than those set within the regulation.
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...