Electrical Connections
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
71
7.2
Connecting mains power supply
7.2.1 Cable requirements
A suitable 3-phase mains supply (with earth and neutral) shall be available to connect
the unit (voltage and frequency must be according to the unit identification plate). The
power supply line must be equipped with necessary protective devices; in particular,
fuses must be of type D
.
7.2.2 Electrical protection requirements
The pre-fuse size should be determined on the basis of the wiring diagram or unit iden-
tification plate and must not exceed the size specified in the above-mentioned docu-
ments. For further information contact your local sales office.
7.2.3 Cable connection
Connect the main power supply cable to the isolator provided within the unit.
ALWAYS
refer to electric wiring diagram supplied with the unit.
If the unit is supplied with an "Automatic Transfer Switch (Dual Power Supply)", this will
be in a different location to the isolator.
7.2.4 Cable routing inside unit
–
Multi
-DENCO units are designed for cable entry from the
BOTTOM
of the unit.
– Secure any interconnecting cables within the unit and ensure that the cables cannot
make contact with the fan or any hot components.
– Do not remove any unused rubber glands or blanking plugs.
– Do NOT drill any holes in the top panels of ANY electrical cabinets.
– Cable routing must consider that some electrical panels can pivot on hinges.
NOTE!
When connecting the supply voltage, make sure to observe the
clockwise rotating
direction
! If the rotation direction is incorrect, an adjustment shall be performed by
changing the phases using the main connection of the unit. Change the phase
sequence of the power supply lines through other.
Never
change the wiring in the unit control cabinet.
NOTE!
If
NO
door interlocked isolator is fitted to the unit, a multi-core cable must be used
for unit power (to avoid cable breaks by the hinged cabinets) and a means of isola-
tion must be provided meet country specific regulations. Always refer to local and
country specific electrical regulations when installing power supplies. A maximum
distance of 1m from the unit is recommended.
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...