Operation
Multi
-DENCO
96
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
9.2.5 Stopping the unit
•
To stop the
Multi
-DENCO unit, simply press the ON/OFF button on the home
screen.
9
The screen will display 'UNIT OFF BY KEYBOARD' if successful.
9.2.6 Disconnecting from power supply
Having deactivated the unit (chapter 9.2.5) and waiting
AT LEAST 5 MINUTES
, you
can disconnect the unit by:
•
Switch the isolator to the 'OFF' position for the outdoor unit (if applicable)
•
Switch the isolator to the 'OFF' position on isolator fitted to the unit (or within 1m)
•
Switch the isolator to the 'OFF' position at the mains distribution board
9.3
Alarms and error messages
Details and explanation of the alarms by
Multi
-DENCO units are available in controller
manual.
Chapter 11 'Fault Finding and Troubleshooting' has details of typical issues than can
be encountered.
Multi
-DENCO units use fans which are regulated independently by the main control
board. Removing guards whilst unit is operational risks death or serious injury.
Inverters also store energy for a period of time after isolation.
•
Disable the unit.
•
Electrically isolate the unit.
•
Wait
AT LEAST
5 minutes.
9
Once fan momentum has ceased and the inverter energy discharged, you can
open the doors and conduct work.
Multi
-DENCO units use fans which are regulated independently by the main control
board. Removing guards whilst unit is operational risks death or serious injury.
Inverters also store energy for a period of time after isolation.
•
Disable the unit.
•
Electrically isolate the unit.
•
Wait
AT LEAST
5 minutes.
9
Once fan momentum has ceased and the inverter energy discharged, you can
open the doors and conduct work.
When the isolator fitted to the unit (or within 1 m) is in the OFF position, the first half
of the isolator could still be live (with electrical power).
•
To ensure safe operations, ensure that the circuit has been isolated in the OFF
position at the mains distribution board and suitably locked to prevent inadvertent
re-connection of electrical power.
NOTICE
Resetting of alarms without rectifying the cause can lead to extended unit damage,
which may result in the voiding of the warranty.
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...