Operation
Multi
-DENCO
94
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
9
Operation
More comprehensive details and explanation on the control and regulation of the
Multi
-DENCO units are available in Controller Manual.
This manual does not cover control of units that have been provided "without controls".
9.1
Requirements
Prior to using a
Multi
-DENCO unit, a full and safe installation and commission must
have been conducted by a suitably qualified personnel and a record of both processes
must be stored. The commissioning report (chapter 13.3) must have been sent to your
local sales office to validate warranty during operation.
Before use all operators
MUST
be familiar with the following:
– The contents of this manual
– Safety assessment for the location where the
Multi
-DENCO unit is situated
– Location of the associated outdoor unit (if applicable)
– Location of power distribution board isolator
– Location of the mains isolator
– Either fitted within the door of the
Multi
-DENCO unit or within 1m of the unit
– Location of circuit breakers (MCBs) inside the
Multi
-DENCO unit
– Shut off (isolation) valves for the
Multi
-DENCO unit including (if applicable):
– Refrigerant circuit
– Chilled Water Circuit
– Hot Water Circuit
– Humidifier Circuit
9.2
General operation
Close control units, like
Multi
-DENCO, are designed for continuous operation to cover
the 8760 hours in a year, thus allowing constant indoor temperatures to be maintained.
9.2.1 Enabling the unit
To enable the unit to operate, you must:
•
Switch the isolator to the 'ON' position at the mains distribution board
•
Switch the isolator to the 'ON' position on isolator fitted to the unit (or within 1 m)
•
Switch the isolator to the 'ON' position for the outdoor unit (if applicable)
•
Wait for the unit to begin its start-up procedure (approximately 45 seconds)
•
Enable the unit by keyboard (see the next chapter for details)
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...