![FläktGroup Multi-DENCO Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/flaktgroup/multi-denco/multi-denco_operation-manual_2302180063.webp)
Multi
-DENCO
Medium Connections
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
63
NOTICE ON WATER USE!
– Under no circumstances should the water supply be fed from a water softening
system.
– Do not add disinfectants or anti-corrosive substances (irritants).
– It is not recommended to use industrial water or chemically and bacteriologically
polluted water for cooling circuits.
– Do not use demineralised water (e.g. osmosis/purified water)
– Where a salt exchange plant is in use at a site, the feed water to the unit should
by-pass this.
Water feed quality
Unit
Normal
tap water
Water with low salt
content
Min.
Max.
Min.
Max.
Activity of hydrogen ions (pH)
–
7
8,5
7
8,5
Specific conductivity 20 °C (
σ
R,20 °C)
μ
S/cm
350
1250
75
350
Dissolved solid materials (cR)
mg/l
(1)
(1)
(1)
(1)
Solid residue at 180 °C (R180)
mg/l
(1)
(1)
(1)
(1)
Total hardness (TH)
mg/l CaCO
3
100 (2)
400
50 (2)
160
Temporary hardness
mg/l CaCO
3
60 (3)
300
30 (3)
100
Iron + manganese
mg/l Fe+Mn
=
0,2
=
0,2
Chlorides
mg/l Cl-
=
30
=
20
Silica
mg/l SiO
2
=
20
=
20
Residual chlorine
mg/l Cl
2
=
0,2
=
0,2
Calcium sulphate
mg/l CaSO
4
=
100
=
60
Metal contamination
mg/l
0
0
0
0
Dissolvents, thinners, detergents, lubricants
mg/l
0
0
0
0
(1)
= General values, depending on specific conductivity: C
R
≅
0,65 x
σ
R,20 °C; R
180
≅
σ
R,20 °C
(2)
= Not below 200 % of chloride content in mg/l Cl
(3) = Not below 300 % of chloride content in mg/l Cl
Tab. 6-5
Содержание Multi-DENCO
Страница 1: ...Multi DENCO OPERATION MANUAL ...
Страница 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Страница 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Страница 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...