Seite/Page 124 - Kaptitel/Chapter 7: Maintenance Instructions
9.12.14
7.9.1.3 Check electrolyte density
Fig. 7.9.1.3-1: Battery
• Measure the electrolyte density of individual cells with a
commercial hydrometer. The hydrometer reading (see table
on following page) indicates the battery’s state of charge.
During measurement, the temperature of the electrolyte
should preferably be 20 °C.
Attention
The gases emitted by the battery are explosive! Keep
sparks and naked flames away from the battery!
Do not allow battery acid to come into contact with skin
or clothing!
Wear protective goggles!
Do not rest tools on the battery!
Electrolyte density
in [kg/ l]
Charge status
Normal
Tropical
1.28
1.23
well charged
1.20
1.12
semi-charged, re-charge
1.12
1.08
discharged, immediately charge
Содержание Panda AGT 6000
Страница 114: ...Installation Instructions Seite Page 114 Kaptitel Chapter 6 Installation Instructions 9 12 14...
Страница 150: ...Seite Page 150 Kapitel Chapter 8 Generator Failure 9 12 14 Leere Seite Intentionally blank Generator Failure...
Страница 158: ...Seite Page 158 Kapitel Chapter 9 Tables 9 12 14 Leere Seite Intentionally blank Tables...
Страница 166: ...Seite Page 166 Kapitel Chapter 10 VCS AGT U I 9 12 14 Leere Seite Intentionally blank VCS AGT U I...
Страница 190: ...Seite Page 190 Kapitel Chapter 12 Generelle Bedienung 9 12 14 Leere Seite Intentionally blank Generelle Bedienung...
Страница 192: ...Seite Page 192 Kapitel Chapter 13 Abmessungen 9 12 14 Leere Seite Intentionally blank Abmessungen...