20.7.15
10.11.2 Electrical connection.
Only special trained persons are allowed to make the electrical connection.
When an extension cable is required, be sure to use a though rubber sheeted flexible and fireproof cable. Limit
length of extension cables depends on the voltage drop along the cable. This drop must be less than 2,5% value of
the nominal output voltage.
Pay attention to the right pin assignment. See “Socket pins of the PMGi” on page 162.
10.11.2.1 Connection to a system with RCD
The PMGi is prepared for the use in a RCD protected grid.,
The PMGi out must be connected 1:1 (PE,N,L) to the customers electrical cabinet. The Life wire and neutral wire will
be connected to the RCD. The PE will be connected to the PE of the electrical cabinet. After installation the function
of the RCD must be tested.
Fig. 10.11-1: PE-N bridge
PE-N Bridge
The PE-N bridge is installed in the prepared jumper terminal.
10.11.2.2 Connection to a system with isolation control
For the use of the PMGi with an isolation controlled grid, the internal PWE-N Bridge must be disconnected.
10.12Technical Data
10.12.1 General Data
PMGi is part of the Panda i-series generator. Its not allowed to be used with other generators or applications.
10.12.2 Generator Specification
1
Storage temperature
PMGi
-20 °C to +55 °C
Working temperature
PMGi
Minimum: -20 °C
Maximum: +40 °C
Maximal internal temperature of the PMGi:
+60 °C
PMG Generator out
3 phase
Voltage Phase
minimum 250 V AC
Maximum 550 V AC
Frequency
minimum 250 Hz
Maximum 650 Hz
Содержание Panda 25i PMS
Страница 10: ...Seite Page 10 Kapitel Chapter 1 20 7 15 Leere Seite Intentionally blank...
Страница 146: ...Generator Failure Seite Page 146 Kaptitel Chapter 8 Generator Failure 20 7 15...
Страница 158: ...Tables Seite Page 158 Kaptitel Chapter 9 Tables 20 7 15...
Страница 180: ...Inverter Panda PMGi 25 Seite Page 180 Kaptitel Chapter 10 Inverter Panda PMGi 25 20 7 15...
Страница 208: ...Seite Page 208 Kapitel Chapter 13 Installation 20 7 15 Leere Seite Intentionally blank Installation...
Страница 210: ...Seite Page 210 Kapitel Chapter 14 Maintenance 20 7 15 Leere Seite Intentionally blank Maintenance...
Страница 216: ...Seite Page 216 Kapitel Chapter 16 Annex 20 7 15 Leere Seite Intentionally blank Annex...