Inverter Panda PMGi 25
Seite/Page 164 - Kaptitel/Chapter 10: Inverter Panda PMGi 25
20.7.15
10.7 Settings for the use of iGenerators with power inverter
ATTENTION: Wrong settings can destroy the
PMGi
For the use of power inverter with the PMGi, the settings of
the power inverter must be modified.
Wrong settings can damage or destroy the PMGi.
The settings for the Victron power inverter must be adapted for the power inverters of other brands.
10.7.1 Settings in the Victron VE Configure II Software - General
Fig. 10.7.1-1: Settings in the Victron VE configure II Software
10.7.1.1 Uninterrupted AC power (UPS function)
Due to the fact that the power inverter connects the shore power immediately to the domestic grid (to fast), the PMGi
gets overloaded and shut down with an error.
UPS Function must be deactivated.
10.7.1.2 Dynamic current limiter
With inductive load the dynamic current limiter will raise up the Voltage in the DC circuit. These over voltage can
damage or destroy the PMGi.
Dynamic current limiter must be deactivated.
Содержание Panda 25i PMS
Страница 10: ...Seite Page 10 Kapitel Chapter 1 20 7 15 Leere Seite Intentionally blank...
Страница 146: ...Generator Failure Seite Page 146 Kaptitel Chapter 8 Generator Failure 20 7 15...
Страница 158: ...Tables Seite Page 158 Kaptitel Chapter 9 Tables 20 7 15...
Страница 180: ...Inverter Panda PMGi 25 Seite Page 180 Kaptitel Chapter 10 Inverter Panda PMGi 25 20 7 15...
Страница 208: ...Seite Page 208 Kapitel Chapter 13 Installation 20 7 15 Leere Seite Intentionally blank Installation...
Страница 210: ...Seite Page 210 Kapitel Chapter 14 Maintenance 20 7 15 Leere Seite Intentionally blank Maintenance...
Страница 216: ...Seite Page 216 Kapitel Chapter 16 Annex 20 7 15 Leere Seite Intentionally blank Annex...