Inverter Panda PMGi 5000
Seite 168 - Kapitel 15: Inverter Panda PMGi 5000
PGMi 5000_eng.fm
Fischer Panda Datenblatt / Datasheet
15.9 Installation of the PMGi
The PMGi must be mounted vertical, with the electrical connection down. So you can read the writing on the PMGi.
The surface where the PMGi is mounted should be smoothed and support the heat transfer. The Air holes and Air
grille must be not covered and enough cooling air must be pleasant at any time for the PMGi.
To mount the PMGi use the four fixing holes diameter 6,5mm.
Note!
See the safety instruction in your Generator and iControl Man-
ual.
The rules of the respective regional authority must be adhered to. Only an electrician may carry out installation of the
electrical connections for safety reasons.
15.9.1 Electrical connection.
Only special trained persons are allowed to make the electrical connection.
When an extension cable is required, be sure to use a though rubber sheeted flexible and fireproof cable. Limit
length of extension cables depends on the voltage drop along the cable. This drop must be less than 2,5% value of
the nominal output voltage.
Pay attention to the right pin assignment. See “Socket pins of the PMGi 5000” on page 163.
15.9.1.1 Connection to a system with RCD
The PMGi is prepared for the use in a RCD protected grid.,
The PMGi out must be connected 1:1 (PE,N,L) to the customers electrical cabinet. The Life wire and neutral wire will
be connected to the RCD. The PE will be connected to the PE of the electrical cabinet. After installation the function
of the RCD must be tested.
Fig. 15.9-1: PE-N bridge
PE-N Bridge
Inside of the PMGi a PE-N bridge
15.9.1.2 Connection to a system with isolation control
For the use of the PMGi with an isolation controlled grid, the internal PWE-N Bridge must be disconnected.
A Manual for this modification can be downloaded under:
1
Содержание 5000i PVK-U
Страница 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Страница 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Страница 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Страница 146: ...Installation Page 146 Chapter 11 Installation 30 10 12 11 3 Dimensions Fig 11 3 0 1 Housing of the Panda iControl2 panel...
Страница 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Страница 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Страница 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...