Seite 166 - Kapitel 15: Inverter Panda PMGi 5000
PGMi 5000_eng.fm
Fischer Panda Datenblatt / Datasheet
15.5.2 Settings in the Victron VE Configure II Software - Inverter
Fig. 15.5.2-1: Settings in the Victron VE configure II Software
15.5.2.1 Assist current boost factor
To reduce the action of the power inverter on the iGenerator, the Assist current boost factor must be reduced from
2.0 to1.3. Wrong settings will cause bad rpm control of the generator.