General operation
Page 134 - Chapter 10: General operation
30.10.12
In the set-up menu of the controller, you can reset the service interval after performing maintenance. See “Set-up
menu” on Page 136.
10.1.3.2 Start-up mode
The start-up mode represents the transition from stand-by mode to operation mode, i.e., generator operation. By
actuating the Start/Stop button in stand-by mode, you can initiate the start-up process of the generator.
The pre-heating is the first step. During this stage, the status field at the top right of the default display screen shows
the word "PREHEAT".
Fig. 10.1.3.2-1: Default display screen during pre-heating
The pre-heating is always implemented for a duration of 10
seconds, regardless of the cylinder head temperature.
In temperatures below 0°C, the pre-heating time is always 40
seconds.
Fig. 10.1.3.2-2: Default display screen during start-up
After pre-heating, the starter is initiated, accompanied by the
text output "STARTING" in the status field of the default display
screen.
Note:
The controller will only perform one starting attempt. If the
generator could not be started, the text output "STARTING
FAILS" informs you of the failure of the generator starting
attempt.
Acknowledging the message with the cursor-up, cursor-down, or the Start/Stop button on the Panda iControl2 panel
will return the system to stand-by mode.
10.1.3.3 Override mode
The override mode follows directly after the successful start-up of the generator. In this mode, no fault analysis is
performed. The duration of the override mode is 10 seconds. The status indicator on the display reads
"OVERRIDE".
Содержание 5000i PVK-U
Страница 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Страница 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Страница 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Страница 146: ...Installation Page 146 Chapter 11 Installation 30 10 12 11 3 Dimensions Fig 11 3 0 1 Housing of the Panda iControl2 panel...
Страница 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Страница 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Страница 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...