General operation
Seite/Page 192 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation
11.3.11
11.4.4.2 Configuration and setting sheet KE02
Standard jumpering for generators with three-phase DC-alternator.
Panel for 24V-operation (over attitude of solder jumper J101 alternatively 12V-operation is possible).
The safety device is installed with the value 0,63AT.
The circuit parts for 24V-operation are not equipped.
Fig. 11.4.4.2-1: Einstellung der Lötjumper für diese Konfiguration (Spalte Konf.)
The solder jumpers are marked on the printed circuit board (with jumper no. and at three-part solder jumper with soldering surface no.)
(1): Equivalent resistance for load control lamp e.g. for use with three-phase alternator also integrated automatic controller of Bosch. The resistance value is 68
Ω
3W,
i.e. only for 12V.
(2): A closed contact switches the appropriate input to GND.
Jumper
Status
Conf.
Description
J1
closed
during operation of the start button heat is along-operated
open
X
Function deactivated
J3
1-2
Dynamo excitation resistor 68R is switched on with Fuel-Pump (1)
2-3
Dynamo excitation resistor 68R is switched on with Panel-ON (1)
open
X
Dynamo excitation resistor is deactivated
J101
closed
12V - operation
open
X
24V - operation
J201
1-2
X
T-Engine-input, for contact, which opens in case of error (2)
2-3
T-Engine-input, for contact, which closes in case of error (2)
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
X
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203
1-2
X
Oil-Press-input, for contact, which opens in case of error (2)
2-3
Oil-Press-input, for contact, which closes in case of error (2)
J204
1-2
X
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
X
T-Winding-input, for contact, which opens in case of error (2)
2-3
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
X
Input Water leak has red LED and switches off
2-3
Input Water leak has yellow LED and does not switch off
J207
1-2
X
Input AC-Fault has red LED and switches off
2-3
Input AC-Fault has yellow LED and does not switch off
J208
1-2
DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3
X
DC-Control-Signal (+) = OK three-phase DC-alternator
J209
1-2
DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3
X
DC-Control-Signal (+) = OK three-phase DC-alternator
J210
closed
Input AC-Fault has Pull-Up-current
≥
10mA
open
X
Input AC-Fault has Pull-Up-current
≥
2,5mA