DTC 100/2 TDG
Technical data
Supply voltage: ............................... 230V, 50Hz +/-10%
Power consumption ........................ 4 VA
Type of thermostat .......................... P
Measurement area ......................... -40°C do 160°C
Adjustable temperature range ........ 10°C - 90°C
Adjustable difference settings ......... 2K - 15K
Hysteresis of difference .................. 1K - 2K
Number of sensors ......................... 2
Output: ........................................... 2x relay: 230V
, 50Hz, 1(1)A, SPST
:
- pump control
- burner control
Inputi: ............................................. 2x sensors
- BSF1- PVC (gray) cable, lenght 1,5m (DHWT sensor)
- KF - Silicon (red) cable, lenght 2m (collector sensor)
Humidity: ......................................... 5% - 70% (non condensed)
Storehouse temperature: ............... 0°C-70°C
Trouble-shooting guide
TROUBLE
POSSIBLE FAILURE
REMEDY
Thermostat inoperative
Plug not connected
Connect plug in socket
Water cools down during night
-Selector switch not in AUTO
position
-One of retaining valves
of the system inoperative
(enables thermosiohon water
circulation)
-Set the switch to AUTO
position
-Check machine installation
We recommend installation of
motor actuated ball valve
When pump is active,
unplesant noise in installation
is heard
Retaining valve makes noise
(weak spring)
Replace nonreturn valve with
motor actuated ball valve
Irrespective of the
temperatures, pump is
inoperative
- Selector switch (2) in position
»OFF« - “T2max.”(1) set too
low(under 20°C)
- Set selector switch (2) to
AUTO position
- Increase T2max
Irrespective of the temp.,
pump is continuosly switched
on.
Selector switch (2) in “ON”
position
Set the switch to AUTO
position
When “T1” key(7) is pressed
Er1 appears
T1 sensor is interrupted
Check T1 senzor
When “T1” (7)key is pressed
Er2 appears
T1 sensor is short circuited
Check T1 senzor
Er1 is shown on display
T2 sensor is interrupted
Check T2 senzor
Er2 is shown on display
T2 sensor is short circuited
Check T2 senzor
Control light of the pump is on,
but the pump is inoperative
Pump bloked or cable of the
pump interrupted
Chek the pump and connection
to regulator
Содержание EMV 110 502 Series
Страница 2: ...page 2...
Страница 4: ...page 4...
Страница 5: ...page 5...
Страница 10: ...page 10...
Страница 11: ...page 11...
Страница 12: ...page 12...
Страница 13: ...page 13...
Страница 14: ...page 14...
Страница 15: ...page 15...
Страница 16: ...page 16...
Страница 17: ...page 17...
Страница 26: ...page 26 EXAMPLES OF USE...
Страница 28: ...page 28...
Страница 29: ...page 29...
Страница 44: ...page 44...
Страница 54: ...page 54 DTC 100 2 TDG HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Страница 57: ...page 57...
Страница 58: ...page 58...
Страница 72: ...page 72 DTC 100 4 TD HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Страница 75: ...page 75...
Страница 76: ...page 76...
Страница 89: ...page 89...
Страница 90: ...page 90...
Страница 103: ...page 103...
Страница 104: ...page 104...