73
®
read no signal more than 4. If more than 4 is observed, realign the UV scanner, and/or shield the
spark from the scanner’s view.
5.
With all methods of flame detection, check pilot flame failure response by manually shutting off
the pilot fuel and then initiate a normal start-up. With no pilot flame present, the control will de-
energize the pilot assembly at the end of the trial for ignition interval, and the control will lock-
out. Also check to verify that the ignition spark does not cause an electrical interference on
infrared or flame rod applications.
Main Flame Test
Note: This test requires an interrupted pilot (a pilot that shuts off after main flame has been estab-
lished).
1.
Proceed through a normal startup. After the pilot flame is shut off, observe the reading on the
display. If the signal reading is low, readjust main flame or realign detector.
2.
Check main flame failure protection by manually shutting off the main fuel supply. Within 4
seconds after main flame goes out, the fuel valve will be de-energized. The alarm circuit will be
energized following safety lockout.
Minimum Pilot Test
This test assures that the flame detector will not detect a pilot flame too small to reliably light off the
main flame. The test should be made on every new installation and following any repositioning or
replacement of the flame detector. This procedure should not be used on a direct spark ignited
burner.
1.
Turn off the main fuel supply manually.
2.
At the start of PTFI, place the Check-run switch in the check position.
3.
Reduce the fuel supply to the pilot until the display reads below 10.
4.
Slowly increase the fuel to the pilot until the display reads 10. This is minimum pilot flame that
the flame detector will reliably detect.
5.
Place the Check-run switch in the Run position. When the main fuel safety shut-off valve is
energized, slowly open the manual main fuel valve.
6.
Observe the light-off of the main flame. It must be smooth and normal.
7.
Repeat the test until a reliable and smooth light-off occurs with the minimum pilot.
8.
After this test is completed, increase the fuel to the pilot to its normal setting.
CAUTION: The minimum pilot test must be accomplished by a trained and qualified
burner technician
CAUTION: If the main flame does not ignite immediately, shut off the main fuel. Realign
the detector to require larger minimum pilot flame
Содержание BurnerLogiX BLL510
Страница 79: ...79 NOTES...