23
®
Modifiable parameters located in PROGRAM SETUP MENU
Shaded parameters not affected by 8 hour burn-in or LOCK SETTINGS.
Refer to SYSTEM INFO Sub Menu, page 49, for language selection.
Parameter
Factory Default
Range
Description
Purge time
00:30s
0:30s – 60:00m, 15 second
increments.
0:10s-60:00m, YP113
0:00s-60:00m, YP115
(0:00s - 60:00m in YP3XX)
Applies to open damper purge time in YP1XX and YP2XX pro-
grammers and to low fire start time in YP3XX programmers.
Count method
DOWN
UP, DOWN
Time counts UP to final value or DOWN to zero from starting
value. This setting will apply to all timer values.
Prove 3-P open at start
NO
YES, NO
Prevents jumped terminals. Requires the 3-P circuit to be
open at the start of a cycle.
PTFI*MTFI timing
10/10*10/15
YP113 = 5/5*3/5
See chart page 18
Applies to terminals 5 and 6 operation during PTFI and MTFI.
Terminal 6 interrupted
or intermittent
INTRP
INTRP, INTMT
Provide interrupted or intermittent operation on terminal 6.
Prove M-8 open
NO
YES, NO
If YES, M-8 must be open at start of open damper purge
period. (YP1XX Series only).
Prove M-D open
NO
YES, NO
If YES, M-D must be open at end of open damper purge
period. Does not apply to YP3XX Series.
Post purge
0:15
0:15s - 1:00m, 5 second
increments.
Selects Post Purge time.
M-D WAIT 10m
YES
YES, NO
Select YES for lockout on M-D open for 10 minutes. Select
NO for indefinite wait for M-D to close. This wait time applies
prior to pilot trial for ignition.
PROVE M-D TFI
NO
YES, NO
Select YES to force lockout on M-D opening during PTFI and
MTFI.
Baud rate
9600
4800, 9600, 19200, 38400
Sets communication baud rate
Unit address
00
00-31
Multi-drop requires unique addressing. Lowest address
allowed for modbus is 01
Lock Settings
NO
YES, NO
Parameters can be stored to memory before automatic 8 hour
store.
DO IR LEARN
NO
YES, NO
Select YES to activate IR LEARN process. See IR operation.
All programmed settings become permanent if the BurnerLogix system has been powered
continuously and 8 hours of main burner (terminal 7) on time has been accumulated. If the
AC power is removed prior to accumulating 8 hours of main burner on time, the system
burn-in time clock will be reset to zero. It is not necessary for the main burner on time to be
continuous. The BurnerLogix accumulates burner on time in seconds. If necessary, the pro-
grammed settings can be made to become permanent anytime before the required 8 hours of
main burner on time through the use of the optional keypad and the LOCK SETTINGS
option under the PROGRAM SETUP sub menu.
Содержание BurnerLogiX BLL510
Страница 79: ...79 NOTES...