5
®
OPERATING TEMPERATURE LIMITS
LOAD RATINGS:
Combination of fuel and igniter terminals
Composition of each combination
Maximum connected load not to exceed 2000 VA
CONTROL
MAXIMUM
MINIMUM
ZB110/ ZB230
140°F
60°C
-40°F
-40°C
YP Programmers
140°F
60°C
-40°F
-40°C
BLV512, VFD Display
140°F
60°C
-40°F
-40°C
BLL510, LCD Display
140°F
60°C
-4°F
-20°C
Scanner UV1A, UV2, UV8A, UV90, 45UV3
200°F
93°C
-40°F
-40°C
45UV5-1005, 45UV5-1105
45UV5-1007, 45UV5-1009
55UV5-1007, 55UV5-1009
200°F
93°C
-40°F
-40°C
48PT2
140°F
60°C
-40°F
-40°C
Flame Rod (Tip 2460°F)
1500°F
816°C
-40°F
-40°C
TS350-X, TS7525-X
Temperature Transducers
185°F
85°C
-13°F
-25°C
BLPS-15, 30, 200, 300
Pressure Transducers
185°F
85°C
-40°F
-40°C
Humidity: 90% R.H. (Non-condensing)
Terminal
Typical Load
A. Maximum Rating
@120V-50/60 Hz
B. Maximum Rating
@230V-50/60 Hz
C. Alternate Rating
M
Burner/Blower Motor
9.8 F.L.A. *
58 L.R.A.
4.0 F.L.A. *
20 L.R.A.
240 VA Pilot Duty
(Motor Starter Coil)
10-11-12-X
Modulator
125 VA Pilot Duty
A
Alarm
50 VA Pilot Duty
Terminal ratings may be selected from either column A or C for 120 VAC or from either column B or C for 30 VAC:
(select the rating from the column which best applies to the connected load on that terminal).
* F.L.A. = full load amps; L.R.A = locked rotor amps
Combination No.
Pilot Fuel
Trm 6
Main
Trm 7
Ignition
Trm 5
Delayed Valve
Trm W
1
C
E
No Load
No Load
2
B
E
No Load
No Load
3
No Load
E
No Load
B
4
E
E
A
No Load
5
No Load
E
A
E
6
D
E
A
No Load
7
D
D
A
D
8
No Load
D
A
No Load
A
B
C
D
E
4.5A Ignition
@120 VAC
50 VA Pilot Duty
plus 4.5A ignition@
120 VAC
180 VA Ignition plus
motor valves with: 660
VA inrush, 360 VA
open, 250 VA hold.
2A Pilot Duty
@120 VAC
65 VA Pilot Duty plus
Motor valves with:
3850 VA inrush, 700
VA open 250 VA hold.
2.2A Ignition
@230 VAC
50 VA Pilot Duty
plus 2.2A ignition
@230 VAC
1A Pilot Duty
@230 VAC