69
®
R = RUN
H = HOLD
L = LOCKOUT C = CHECK
DEC
HEX
STATE
TERMINAL
YZ300 INTERLOCK ANNUNCIATOR LOCKOUT MESSAGES
41
29
L
3-43
HIGH WATER
42
2A
L
43-44
LOW WATER
43
2B
L
51-52
HIGH GAS PRESSURE
44
2C
L
50-51
LOW GAS PRESSURE
92
5C
L
52-54
AUX GAS
45
2D
L
47-48
LOW OIL PRESSURE
56
38
L
44-46
HIGH OIL TEMPERATURE
46
2E
L
46-47
LOW OIL TEMPERATURE
47
2F
L
48-50
LOW ATOMIZING MEDIA
48
30
L
54-55
HIGH PRESSURE
49
31
L
55-56
HIGH TEMPERATURE
50
32
L
56-57
AUX #4 OPEN
51
33
L
57-58
AUX #5 OPEN
52
34
L
58-59
AUX #6 OPEN
53
35
L
59-60
AUX #7 OPEN
40
28
L
60-P
AIR FLOW OPEN
DEC
HEX
STATE
TERMINAL
YZ300 INTERLOCK ANNUNCIATOR HOLD MESSAGES
94
5E
H
L1-40
OP CONTROL OPEN
60
3C
H
40-41
L1-3 AUX #1 OPEN
61
3D
H
41-42
L1-3 AUX #2 OPEN
62
3E
H
42-3
L1-3 AUX #3 OPEN
63
3F
H-C
3-43
HIGH WATER
64
40
H-C
43-44
LOW WATER
65
41
H-C
51-52
HIGH GAS PRESSURE
66
42
H-C
50-51
LOW GAS PRESSURE
95
5F
H-C
52-54
AUX GAS
67
43
H-C
47-48
LOW OIL PRESSURE
96
60
H-C
44-46
HIGH OIL TEMPERATURE
68
44
H-C
46-47
LOW OIL TEMPERATURE
69
45
H-C
48-50
LOW ATOMIZING MEDIA
70
46
H-C
54-55
HIGH PRESSURE
71
47
H-C
55-56
HIGH TEMPERATURE
72
48
H-C
56-57
AUX #4 OPEN
73
49
H-C
57-58
AUX #5 OPEN
74
4A
H-C
58-58
AUX #6 OPEN
75
4B
H-C
59-60
AUX #7 OPEN
5
5
H-C
60-P
AIR FLOW OPEN
Содержание BurnerLogiX BLL510