13
®
PRESSURE AND TEMPERATURE SENSORS
1.
Insure that the range of the selected pressure or temperature sensor is appropriate for the
application. See Table 2
Table 2:
2.
Note: A general rule to follow when selecting the sensor range is that the expected value of the
monitored pressure or sensor should fall between 40-70% of the upper range of the sensor. For
example, a steam boiler maintains 20 lbs. pressure, select the BLPS-30 Pressure Sensor, with a
0-30 psig range.
3.
The sensors must be located where the ambient temperature will not exceed the maximum ambi-
ent operating temperature specified for the sensor.
4.
Insure that the pressure range programmed on the BurnerLogix Z Control matches the installed
pressure sensor.
5.
Do not mount any of the sensors where they could be used as a footstep.
Installation must be performed by a trained, experienced flame safeguard technician.
MOUNTING PRESSURE SENSORS
Note: refer to Figure 3
1.
The steam pressure sensors (BLPS-15, -30, -200, -300) provide a 1/4" NPT female fitting for
connection to the steam header.
2.
Make sure the boiler is shut down and zero steam pressure exists in the boiler vessel.
3.
Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
steam pressure sensor.
4.
Always mount the steam pressure sensor above the water line of the boiler.
5.
Locate the pressure sensors where the ambient temperature will not exceed 185F
6.
Use only a small amount of pipe compound to seal the connection joints. Excess pipe compound
may clog the fitting and prevent proper operation of the sensor.
Part
Number
Sensor Type Set Point Range
Cut In
Cut Out
Mod Range
Increment
Decrement
0 - 15.0 psi
1.0 - 14.0psi
0 - 6.0psi
0.3 - 6.0psi
0.3 - 6.0psi
0.1psi
0 - 1030mb
70 - 960mb
0 - 410mb
20 - 410mb
20 - 410mb
10mb
0 - 30.0 psi
1.0 - 28.0psi
0 - 6.0psi
0.3 - 6.0psi
0.3 - 6.0psi
0.1psi
0 - 2070mb
70 - 1930mb
0 - 410mb
20 - 410mb
20 - 410mb
10mb
0 - 200 psi
10 - 190psi
0 - 60psi
3 - 60psi
3 - 60psi
1.0psi
0 - 13.8b
0.7 - 13b
0 - 4.1b
0.2 - 4.1b
0.2 - 4.1b
.05b
0 - 300 psi
10 - 280psi
0 - 60psi
3 - 60psi
3 - 60psi
1.0psi
0 - 20.7b
0.7 - 19.3b
0 - 4.1b
0.2 - 4.10b
0.2 - 4.10b
.05b
32º - 350ºF
36º - 338ºF
0º - 60ºF
3º - 60ºF
3º - 60ºF
1ºF
0º - 176ºC
4º - 170ºC
0º - 60ºC
3º - 60ºC
3º - 60ºC
1ºC
32º - 752ºF
36º - 725ºF
0º - 60ºF
3º - 60ºF
3º - 60ºF
1ºF
0º - 400ºC
4º - 385ºC
0º - 60ºC
3º - 60ºC
3º - 60ºC
1ºC
BLPS-15
BLPS-30
BLPS-200
BLPS-300
mb = millibar, p = psi, b = bar
Note: 1 psi = 68.9 mbar
TS350-X*
TS752-X*
*Select Length X = -2”, -4” or -8”
Содержание BurnerLogiX BLL510