18
®
PTFI*MTFI TIMINGS
The BurnerLogix system provides keypad selectable timings for both PTFI and MTFI. The selec-
tions offered can provide 5 or 10 second timing for terminal 5 and 6 or a shortened time for terminal
5, allowing for early spark termination. BurnerLogix also provides selectable interrupted or intermit-
tent operation for terminal 6.
The selections provided for PTFI*MTFI timings are:
Table 3:
FIREYE
PART
NUMBER
Pre-purge
Programming
(Seconds)
Proven
High Fire
Interlock
(M-8)
Proven
Low Fire
Interlock
(M-D)
Terminal 6,
Interrupted
or
Intermittent
Early Spark
Termination
PTFI
(5/6)
MTFI
(5/6)
Running
Interlock
(3-P)
Flame Fail
Time
(Seconds)
Firing
Rate
Motor
SETTINGS SHOWN ARE FACTORY DEFAULT
YP100
30
YES
YES
INTRP
NO
10/10
10/15
Non-recycle
4
YES
YP102
30
YES
YES
INTRP
NO
10/10
10/15
Non-recycle
2
YES
YP138
30
YES
YES
INTRP
NO
10/10
10/15
Non-recycle
4
YES
YP118
30
YES
YES
INTRP
NO
10/10
10/15
Non-recycle
1
YES
YP183
30
YES
YES
INTRP
NO
10/10
10/15
Non-recycle
4
YES
YP113
30
YES
YES
INTRP
NO
5/5
3/5
Non-recycle
1
YES
YP115
30
YES
YES
INTRP
NO
5/5
3/5
Non-recycle
1
YES
SELECTION
PTFI
MTFI
COMMENT
Term 5
Term 6
Term 5
Term 6
10/10*10/15
10
10
10
15
5/5*0/10
5
5
0
10
NO SPARK DURING MTFI
5/5*0/5
5
5
0
5
NO SPARK DURING MTFI
5/5*10/15
5
5
10
15
SHORTENED PTFI
5/5*10/10
5
5
10
10
SHORTENED PTFI
5/10*0/15
5
10
0
15
EARLY SPARK TERMINATION
5/10*0/10
5
10
0
10
EARLY SPARK TERMINATION
10/10*0/10
10
10
0
10
NO SPARK DURING MTFI
10/10*0/5
10
10
0
5
NO SPARK DURING MTFI
10/10*10/10
10
10
10
10
Содержание BurnerLogiX BLL510