12
®
The location should be free from excessive vibration and within the ambient temperature rating.
FIGURE 2.
WIRING BASE CONNECTIONS (shown for 120 VAC)
UL does not apply to 230 VAC operations
Terminal No.
60-2852-1
60-2854-1
Wire Color
60-2850-1
Type
Description
Rating
L1 (Hot)
Black
Line voltage supply
120 VAC (+10%, -15%), 50/60 Hz
L2 (Neutral)
White
Line voltage common
EARTH
Green
Ground
S1
Red/Wht
Scanner Input
300 VAC, 3 mA (UV models)
15 VDC (IR models)
S2
Blu/Wht
Scanner Input
300 VAC, 3 mA (UV models)
0 VDC (IR models)
A
Red
Output
Alarm
120 VAC, 1 A pilot duty
M
Brown
Output
Combustion Blower
120 VAC, 9.8 FLA, 58.8 LRA
3
Yellow
Input
Operating Control
120 VAC, 1 mA
13
Orange
Input
Fuel Valve End Switch,
Pre-Ignition Interlock
120 VAC, 1 mA
P
Gray
Input
Running Interlock
120 VAC, 1 mA
D
Wht/Brn
Input
Low Fire Start Switch
120 VAC, 1 mA
8
Wht/Gry
Input
Open Damper Proving Switch
120 VAC, 1 mA
W
Wht/Orn
Output
Delayed Main Valve
See Load Ratings
5
LT Blue
Output
Ignition / Pilot Valve
See Load Ratings
6
Tan
Output
Pilot Valve
See Load Ratings
7
Violet
Output
Main Fuel Valve
See Load Ratings
16
DK Blue
Input
Lag 1 Input
See description for
alternate uses
21
Pink
Input
Lag 2 Input
LOW VOLTAGE INPUT/OUTPUT
12
Wht/Yel
Output
Modulator Drive Positive
4-20mA Output
10
Wht/Red
Output
Modulator Drive Common
X
Wht/Blue
Output
Temp/Pressure Source Voltage
28 vdc Nominal
11
Wht/Grn
Input
Temp/Pressure #1 (PCV)
4-20mA Input, Primary Control Variable
22
Wht/Vio
Input
Temp/Pressure #2 (AUX 1)
4-20mA Input
23
Brn/Wht
Input
Temp/Pressure #3(AUX 2)
4-20mA Input