MINIMUM HEIGHT OF FLUE SYSTEM OUTLET
NOTES:
1.
The flue shall extend not less than 4.6m above the top of the floor protec-
tor.
2.
The flue cowl must be at least 600mm above the highest point of the roof if
within 3 metres of it, or 1 metre above the roof penetration if more than 3
metres from the ridge.
3.
No part of the building, or any adjacent building may be in or above a
circular area of a horizontal radius of 3 metres from the flue exit.