P/N 06-632, Rev 0
OPERATING INSTRUCTIONS
CyberCat
®
Control System
(P/N 10-064/10-066)
Commercial Protected Premises Control Unit
Local, Auxiliary, Remote Station (PPU), Central Station (PPU), and Releasing Service
These instructions must be framed and displayed next to the panel in accordance with NFPA 72, National Fire Alarm Code for Local
Fire Alarm System.
The key to open the panel can be found at this location:
____________________________________________
1.0 OPERATING INFORMATION
Normal Standby
1. Green AC Power LED lit steady.
2. All notification appliances off.
System Alarm
1. Red Alarm LED flashes.
2. Local piezo pulses.
3. Alarm notification appliances on.
4. Alarm information visible on LCD (liquid crystal display).
5. DO NOT press the RESET button at this time.
6. Press the ACKNOWLEDGE button to turn off the local
piezo. Flashing LEDs will illuminate steady after button
press.
7. Press the SILENCE button to turn off the local piezo and
silence active notification appliances programmed for
silence. Yellow silence LED will illuminate steady after
button press.
8. Press the F1 button to display the source of the event on
the top line of the LCD (liquid crystal display).
9. Investigate the source of the alarm condition and take
appropriate actions.
10. After correcting the Alarm condition, press the RESET
button to restore the system to normal operation.
System Trouble/Supervisory
1. Yellow Trouble and/or Supervisory LED flashes.
2. Local piezo pulses.
3. Trouble and/or Supervisory notification appliances on.
4. Trouble and/or Supervisory information visible on LCD
(liquid crystal display).
5. DO NOT press the RESET button at this time.
6. Press the ACKNOWLEDGE button to turn off the local
piezo. Flashing LEDs will illuminate steady after button
press.
7. Press the SILENCE button to turn off the local piezo and
silence active notification appliances programmed for
silence. Yellow silence LED will illuminate steady after
button press.
8. Press the F1 button to display the source of the event on
the top line of the LCD (liquid crystal display).
9. Investigate the source of the Trouble/Supervisory condition
and take appropriate actions.
10. After correcting the Trouble/Supervisory condition, press
the RESET button to restore the system to normal
operation.
Trouble Condition
– Activation of a trouble signal under
normal operation indicates a problem with the system (not an
alarm) that requires immediate attention. Contact your local
service representative. In most trouble conditions, the fire
alarm system continues to provide protection to the building
and its occupants; however, trouble conditions should not be
allowed to remain and should be investigated and remedied as
soon as possible to ensure proper system operation.
2.0 HISTORY AND CONTROL BUTTONS
Step Alarm
– Steps through the current ALARM events stored
in the panel’s Alarm history buffer. Available only if there are
active alarm events present on the system.
Step Super
– Steps through the current SUPERVISORY
events stored in the panel’s Supervisory history buffer.
Available only if there are active supervisory events present on
the system.
Step Trouble
- Steps through the current TROUBLE events
stored in the panel’s Trouble history buffer. Available only if
there are active trouble events present on the system.
Step All
- Steps through ALL events stored in the panel’s
current event history buffer. Press the F5 button to toggle
between current events and the panel’s entire 3,200 event
history buffer.
Drill
– Manually activates all outputs and notification appliances
circuits assigned for drill operation in the configuration. Press
the RESET button to clear the drill activation. Displays drill
activation on LCD (liquid crystal display).
Acknowledge
– Silences the local piezo sounder and changes
all flashing LEDs to steady. All outputs remain active. Creates
an acknowledge event in the panel history buffer.
Silence
– Silences the local piezo sounder and all silenceable
circuits. Illuminates the Yellow SILENCE LED steady and
creates a silence event in the panel history buffer.
Reset
– Resets the control panel to normal operation. All
active control functions (relays and NACs) will deactivate. All
display LEDs will illuminate steady until reset is complete. If
events are still present on the system, control functions will
immediately activate.
Escape
– Toggles event display from OFF-NORMAL (events
present) to SYSTEM NORMAL (no events present) to TOP
LEVEL menu.
Function Buttons (F1 – F6)
– Used to navigate through the
control panel’s menu system during system operation,
maintenance and configuration.