4.0 INSTALLATION
4-18
CyberCat 254/1016 Installation Manual
UL S2203
Rev 14, 09/2015
P/N: 06-326
FM
P6
(DACT) is dedicated for connection of the optional internal Fire Communicator as shown in Exhibit 4-19.
Refer to Fike document 06-479 for more details.
4.16.4 AUXILIARY POWER WIRING (P7)
The panel provides one power-limited 24VDC, resettable
power output (two leftmost contacts on P7) as shown in
Exhibit 4-20. This power output is used for devices that
latch events and require removal of power to reset such
as 4-wire detectors, some duct detectors, beam
detectors, etc. It is rated at 2 amps maximum and is
supervised.
The remaining two sets of power outputs on P7 are
power-limited 24VDC, non-resettable power outputs.
This power output is used for addressable output
modules, graphic annunciators, remote displays, etc.
Each circuit is rated at 2 amps maximum and is
supervised.
Shielded wire is not required, but if used land outgoing
drain wire to terminal marked SHLD. Connect it through
and insulate at each junction box and leave unconnected
and insulated at the last device.
Note:
The standard CyberCat Control Panel has a
total power capability of 6 amps.
Exhibit 4-19: (P6) RS485 DACT Wiring
Exhibit 4-20: (P7) Auxiliary Power Wiring