3.0 SYSTEM COMPONENTS
UL S2203
CyberCat 254/1016 Installation Manual
3-7
FM
P/N: 06-326
Rev 14, 09/2015
Exhibit 3-8: CyberCat Controller Terminal Specifications – Cont.
Terminal
Block
Terminal
Labels
Function and Electrical
Ratings/Requirements
Wiring Requirements
P13
•
Provides connection point for an optional
CRM4 relay module (P/N 10-2204) or an
RPM reverse polarity module (P/N 10-
2254)
•
If P20 is occupied by a Network module,
the P13 terminal is not available
All CRM4 connections shall be power
limited or non-power limited, not both
See Section 4.11
P14
No
Connection
P15
•
Connects optional Supplemental Loop
Module, P/N 10-2473 to the CyberCat
1016 controller
•
SLM is NOT compatible with the
CyberCat 254 controller
See Section 4.11
P16
•
Connects optional Supplemental Power
Supply Module, P/N 10-2474-P to the
CyberCat 1016 controller
•
SPS is NOT compatible with the
CyberCat 254 controller
See Section 4.11
P17
•
For Fike use only
P18
•
For Fike use only
P19
•
Controller display interface (keypad and
LEDs)
P20
•
Provides connection point for an optional
RS485 network module (P/N 10-2482) or
Fiber Optic network module (P/N 10-
2624)
•
If P13 is occupied by a CRM4 or RPM
module, the P20 terminal is not available
See Section 4.11
P21
No
Connection
P22
•
Controller display interface (LCD only)
TP1
•
CyberCat controller ground reference test
point
•
Use when making DC voltage
measurements on the control board
•
Normal ground fault limits (TP1 to
Chassis): 2.17 VDC nominal for Level 1
and 5 VDC nominal for Level 2. If a
ground fault is present, voltage will sway
in either direction.
Ground fault detection impedances are 60K
Ω
between power ground and chassis
ground or 1M
Ω
between main power and
chassis ground
TP2
•
Positive (+) side of the CyberCat
controller 24 VDC power bus
•
To verify controller voltage, connect
positive lead of voltmeter to TP2 and
ground lead of voltmeter to TP1