2.0 SYSTEM OVERVIEW
2-2
CyberCat 254/1016 Installation Manual
UL S2203
Rev 14, 09/2015
P/N: 06-326
FM
2.1.1
CYBERCAT FEATURES
GENERAL
♦
Two 24V DC, 2A NAC (audible) circuits on main board
with integrated synchronization
♦
Available with and without integral
SERIAL, Point ID
DACT interface
♦
253 user defined zones
♦
Removable terminal blocks for field wiring
♦
80 character, backlit LCD display
♦
Local piezo with distinct event tones
♦
Real time clock
♦
10 Status LED’s to easily identify system status
♦
3200 event history buffer
♦
Compatible with internal or external Firefighter’s Smoke
Control Station Modules
♦
Critical process monitoring
♦
One-person Walktest capability
♦
Supports ability to network up to 128 nodes (each could
be CyberCat 254 or 1016)
♦
Disable by point/circuit or zone
♦
Drill function at panel and remote
♦
Emergency Voice/Alarm Communication via panel’s
RS485 peripheral bus
♦
Provides solenoid releasing operation
♦
Alarm verification
♦
Supports up to 31 peripheral devices (i.e. Remote
Display, LED Graphics, and Smoke Control Switch
Cards)
♦
Easy to add/remove devices
♦
Diagnostic menus
♦
Approved Security Function for FIPS PUB 140-2: NO ENCRYPTION EMPLOYED
- Communication Security: Level 0
- Stored Data Security: Level 0
- Access Control Security: Level 0
- Physical Security: Level 1
- Audit Control: Not Provided
POWER
♦
6 amps useable alarm power, 2A standby- CyberCat 1016 expandable to 12 amps alarm power, 4 A standby
♦
Operation from 120VAC/ 60 Hz or 240VAC 50 /60Hz
♦
Two 24V DC, 2A continuous auxiliary power outputs (CyberCat 1016 Expandable to 5 circuits with SPS)
♦
One 24V DC, 2A resettable auxiliary power output
♦
Supports up to 75 AH of batteries, CyberCat 1016 expandable to 150 AH using SPS
SIGNALING LINE CIRCUIT
♦
Address devices with Infrared (IR) tool, similar to remote control device, non-listed.
♦
CyberCat 254 = One addressable loop, 254 devices per loop.
♦
CyberCat 1016 = Two addressable loops expandable to four, 254 devices per loop, maximum 1016 devices.
♦
Loops can be wired NFPA Class B, A or X with isolator devices.
♦
True peer-to-peer digital protocol for extremely fast and reliable communications
♦
Addressable Device “learn” and “auto-program” functions
♦
Automatic day/night sensitivity adjustment
♦
Automatic holiday sensitivity adjustment
♦
New
Acclimate operation for detectors
♦
IR Tool provides ability to read sensitivity levels or perform remote test of device
♦
Devices contain multi-color LED for quick reference of device status
♦
Detectors provide early warning pre-alarm detection and can also provide a summing feature (up to 8 detectors), non-
listed.
♦
Sounder or Relay Bases fully programmable
♦
Optional Remote LED can be added to a detector base, programmable for any device, zone/state
ENCLOSURE
♦
Three enclosures sizes are available to suit system requirements
♦
Enclosures are equipped with a 0.50” wide lip to facilitate flush mounting
♦
Removable door and dead-front panel options for ease of installation
♦
Internal dead-front door options available
♦
Available in Red or Black