![Fike CyberCat 1016 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/fike/cybercat-1016/cybercat-1016_installation-manual_2288410041.webp)
3.0 SYSTEM COMPONENTS
UL S2203
CyberCat 254/1016 Installation Manual
3-21
FM
P/N: 06-326
Rev 14, 09/2015
3.6.6
INTELLIGENT GRAPHIC ANNUNCIATOR
The LED Graphic (See Exhibit 3-35) is a custom made graphic
display that provides a specific building layout pictorial with the
actual fire alarm devices indicated with a color status LED (red,
green, yellow or orange). When an event occurs, the intelligent data
will be transferred via the RS485 output to the graphic and the
specific device or zone LED will light as programmed.
Refer to Fike document 06-231, for more information.
3.6.7
FIREFIGHTER’S SMOKE CONTROL STATION (FSCS)
The Firefighter Smoke Control Station (See Exhibit 3-36) is a custom
made graphic display that provides a specific building layout pictorial
with Smoke Control override switches and LEDs to indicate the
status of the air handling equipment and dampers utilized for the
building smoke management system.
When a switch override function is initiated, the corresponding LED
to override will flash until confirmation that the desired state of the air
handling equipment has been achieved. Upon receipt of
confirmation, the LED will transition from flashing to continuously on.
Refer to Fike document 06-447, for more information.
Exhibit 3-35: Graphic Annunciator
Exhibit 3-36: Firefighter’s
Smoke Control Station (FSCS)