3.0 SYSTEM COMPONENTS
3-12
CyberCat 254/1016 Installation Manual
UL S2203
Rev 14, 09/2015
P/N: 06-326
FM
Exhibit 3-14: FCC Enclosure with
Twenty-Three Card Dead-front
3.3.2.2
FCC ENCLOSURE WITH TWENTY-THREE CARD DEAD-FRONT
CyberCat 1016 Enclosure (P/N 10-2483-
c
-L-23-
o
)
CyberCat 254 Enclosure (P/N 10-2527-
c
-L-23-
o
)
c
= enclosure color,
R
ed or
B
lack
o
= outer door overlay color,
R
ed or
B
lack
The FCC enclosure with twenty-three card dead-front door
(See Exhibit 3-14) is equipped with threaded press studs in
the enclosure back-box that allows easy installation of the
following CyberCat system components:
•
CyberCat Controller with extended display
•
CyberCat AC Power transformers (qty. 2)*
•
Bosch FPT-DACT-LC, P/N 10-2528
•
Class A Peripheral Bus Card, P/N 10-2792*
•
Multi-Interface Module (MIM), P/N 10-2583*
•
Ethernet Module, P/N 10-2627*
•
FCC Digital Paging Card, P/N 10-2727
•
Amplifier Kit, P/N 10-2773**
•
Amplifier Audio Transformer, P/N 02-12825
•
Amplifier AC Transformer
•
Relay Control Card, P/N 10-2785**
•
Two 18AH batteries (maximum)
The dead-front door is equipped with threaded press studs that allow easy mounting of any of the following
optional cards (sold separately):
•
CyberCat Extended Display, P/N 10-2680
•
Twenty-Three (23) dead-front switch cards
−
Smoke Control switch card, P/N 10-2658
−
Input/Output switch card, P/N 10-2659
−
Annunciator card, P/N 10-2660
−
Audio Control card, P/N 10-2661
−
Fire-Phone card, P/N 10-2728
−
Supplemental fire-phone card, P/N 10-2730
−
FCC Paging Control card, P/N 10-2741
−
City Tie Disconnect switch, P/N 10-2721
Refer to Fike document 06-570 for FCC enclosure installation details.
*Secondary power transformer, MIM, Ethernet Module and
Class A Peripheral Bus Card all share a common mounting
location within the enclosure. Only one component can be
installed at this location.
**Amplifier Card and Relay Control Card share a common
mounting location. Only one component can be installed at
this location.