3.0 SYSTEM COMPONENTS
3-14
CyberCat 254/1016 Installation Manual
UL S2203
Rev 14, 09/2015
P/N: 06-326
FM
Exhibit 3-15: FCC Enclosure with
Twenty-Five Card Dead-front
3.3.3
FIRE COMMAND CENTER ENCLOSURE (FCC)
WITH TWENTY-FIVE CARD DEAD-FRONT
Enclosure P/N 10-2772-
c
-
o
c
= enclosure color,
R
ed or
B
lack
o
= door panel overlay color,
R
ed or
B
lack
The FCC enclosure with a twenty-five card dead-front door
(See Exhibit 3-15) is designed to allow additional control and
annunciator cards to be easily added to the system.
Threaded press studs are supplied in the enclosure back-
box for easy installation of the following CyberCat system
components:
•
Amplifier Card, P/N 10-2726
•
Amplifier Audio Transformer, P/N 02-12825
•
Amplifier AC Power Transformer
•
Multi-Interface Module (MIM), P/N 10-2583
•
Ethernet Module, P/N 10-2627
•
Two 18 AH batteries (maximum)
Threaded press studs are supplied on the inner dead-front
door for easy installation of up to twenty-five of the dead-
front cards listed below:
−
Smoke Control switch card, P/N 10-2658
−
Input/Output switch card, P/N 10-2659
−
Annunciator card, P/N 10-2660
−
Audio Control card, P/N 10-2661
−
Fire-Phone Card, P/N 10-2728
−
Supplemental fire-phone card, P/N 10-2730
−
City Tie Disconnect switch, P/N 10-2721
Refer to Fike document 06-570 for FCC enclosure installation details.
Note:
This enclosure cannot be used to mount the CyberCat controller as there is no location for
mounting of the system display.