The AKAS® displays messages by serial transfer via its RS 232 interface; transfer format: 9600 baud, 1 start
bit, 8 data bits, 1 stop bit. The messages have even parity and will be repeated at least three times. The time
gap between 2 messages is at least 100 ms. At the receiver, defective messages are gated, because only tho-
se messages are accpted that fulfil the following conditions: an even parity, successful reception of the message
is provided if it is received at least 3 consecutive times and if its complete compatibility to one of the message
possibilities indicated below is given.
There are different kinds of messages:
- Information concerning the status
of the AKAS® or
handling directions
for the operator,
here are Bit 0 and Bit 1 = 1,
-
Warnings
concerning errors that, if received three times one immediately after the other, may lead to the in-
terlocking of the AKAS®, here is Bit 0 = 0 and Bit 1 = 1,
-
Error reports
of the interlocked AKAS® , here is Bit 0 = 1 and Bit 1 = 0.
Electrical connections - Description / Wiring diagrams
Displaying outputs
37
Status messages,
warnings and Error
reports via the RS 232
serial interface
Status messages, handling di-
rections for the operator
(binary xxxxxx11)
6
6.6
background grey: ((other
message or no message,
if monitoring functions are
partially cancelled)
Doku Nr. 995 Stand 1.12.2011 / Aui
message
transferred
byte
decimal
operating mode
description
possible text in the display sy-
stem
handling directions
3
3
antivalent foot pe-
dal inputs without
protective circuit
monitoring
front reset button does not
enable
normally closed contact of
the foot pedal does not ena-
ble
verify reset button and cable leading to the normally
closed contact of the foot pedal if interrupted
verify the cable leading to the normally closed con-
tact of the foot pedal if interrupted
3
7
15
15
equivalent foot pe-
dal inputs
error at the request for
release of the closing stroke
Mutinglamp does not light
up
without overrun
traverse control
Stop at the overrun traverse
cam
-
check the equivalent switching lines going FUO and
FUS . They are evaluated as "different"
see message 63
during overrun traverse test
-
23
39
43
43
open the press completely
in order to quit the safety
point range
release foot pedal
without overrun
traverse control
overrun traverse OK
-
51
51
51
51
without EDM
rear reset buuton is defecti-
ve or the EDM is not in Stop
status
rear RESET button is de-
fective
without protective
circuit monitoring
without EDM and
without protective
circuit monitoring
EDM is not in Stop Status
wrong poetntial at EDMO
or EDMS
if this message is displayed after every pressing and
releasing of the foot pedal, check the SP connecting
circuit for short circuits
during overrun traverse test
-
check rear reset button for short-circuits
check rear reset button for short circuit
Check EDM Signals
check the connectors for short circuits
63
83
83
95
Mutinglamp does not light
up
overrun traverse too long
without overrun
traverse control
-
overrun traverse mearue-
ment has not been carried
out
95
without overrun
traverse control
-
open the press completely. If this message is repea-
ted at the following new stroke and the internal mu-
ting lamp does not light up,there is an internal error at
the version that has no connection option of an exter-
nal muting lamp. With the version with external con-
nection option of an external Muting lamp, the con-
nection KAST must be checked for short-circuits on -.
during overrun traverse test
-
possible reasoin: the protective field is interrupted, or
the protective circuit is interrupted, or the foor pedal is
released, or no fast speed during the overrun traverse
measurement, evtl. because the stroke for the ober-
run traverse measurement has not been started by
the UDC of the machine. Open the press completely
and carry out a new stroke for the overrun traverse
measurement.
-