Electrical connections - Description / Wiring diagrams
6
-with integrated safety functions
6.5.1
Doku Nr. 995 Stand 1.12.2011 / Aui
A selector switch provides the possibility to choose between operating mode with activated protective
field of the AKAS® and fast closing speed or operating mode with protection only by monitored slow
speed closing, see
Wiring diagrams 8/S.32 und 9/S.32
. If the selector switch is activated, the protective
field of the AKAS® is muted (bridged). This state is displayed by the shining muting lamp. By disabling
of its
output
SGA
, AKAS® requires the NC to carry out only cycles in slow speed, which is monitored
by the AKAS®. Given the fact that in this operating mode, only cycles in slow speed are possible, the la-
teral protective grids are not monitored. Every switching-over of the selector, the reset buttomn must be
activated for the Emergency-OFF circuits and the circuits of the lateralprotective doors.
7. Installation operating mo-
de, i.e. protection by monito-
res slow speed without avti-
vated protective field
during operation with door
monitoring
operation with equivalent switching
protective door contacts
operation with antivalent switching
protective door contacts
NA1
NA3
NA2
EDMO
.
.
.
FUO
.
.
.
+ 24V
Wiring diagram
8
/S.32
Emergency OFF 1
Emergency OFF 2
Reset button for
Emergency OFF,
lateral protective
grids and selector
switch
operation with
activated protective field of the AKAS® and slow speed closing movement
(selector not activated)
operation with
only protection by monitored slow speed closing movement
(selector switch activated)
selector switch
not activated
right lateral protec-
tive grid (open)
left lateral protecti-
ve grid (open)
rear protective
grids (open)
depending on
operation mode
further contacts
Reset button for
rear protective
grids
NA1
NA3
NA2
EDMO
.
.
.
FUO
.
.
.
+24 V
Wiring diagram
9
/S.32
Reset button for
Emergency OFF,
lateral protective
grids and selector
switch
Reset button for
rear protective
grids
depending on
operation mode
further contacts
Emergency OFF 1
Emergency OFF 2
selector switch
not activated
right lateral protec-
tive grid (open)
left lateral protecti-
ve grid (open)
rear protective
grids (open)
operation with
activated protective field of the AKAS® and slow speed closing movement
(selector not activated)
operation with
only protection by monitored slow speed closing movement
(selector switch activated)
AKAS®-LC II F
FIESSLER
E L E K T R O N I K