The Hex-switches must always be programmed in pairs (1 and 3,
2 and 4). Within each pair, equal values must be programmed.
2.
Operating modes with additional Safety control
(e.g.. Safety PLC
FPSC
)
example
:
35
Electrical connections - Description / Wiring diagrams
6
Programming of the integrated safety functions via Hex-switches
6.5.2
Doku Nr. 995 Stand 1.12.2011 / Aui
Hex-switch
2 and 4
Hex-switchpo-
sitions
EDM
Stop valve
monito-
ring
slow speed
traverse in-
formation
*
switching over
tolerance enhance-
ment of the valve
position monitors
0
1
without
without
without
without
+ 0 ms
+100 ms
2
3
4
5
without
without
without
without
without
without
with
with
+ 200 ms
+ 300 ms
+ 0 ms
+100 ms
6
7
without
without
with
with
+ 200 ms
+ 300 ms
Hex-switch
1 and 3
Hex-switchpo-
sitions
Monitoring of
the foot pedal
antivalent
inputs for
release of
closing stro-
ke FUS / FUO
overrun
traverse
control
Monitoring of
protective doors
/ Emergency OFF
equivalent switching
0
1
without
without
equivalent
equivalent
without
without
without
with
2
3
4
5
without
without
equivalent
equivalent
with
with
antivalent
antivalent
with
with
without
with
without
without
without
with
6
7
with
with
antivalent
antivalent
with
with
without
with
start / stop of closing stroke
Hex-switch
2 and 4
Hex-switchpo-
sitions
EDM
Stop valve
monito-
ring
slow speed
traverse in-
formation
*
switching over
tolerance enhance-
ment of the valve
position monitors
1
without
without
+100 ms
Hex-switch
1 and 3
Hex-switchpo-
sitions
Monitoring of
the foot pedal
antivalent
inputs for
release of
closing stro-
ke FUS / FUO
overrun
traverse
control
Monitoring of
protective doors
/ Emergency OFF
equivalent switching
3
without
equivalent
with
with
start / stop of closing stroke
Hex switch
1
2
3
4
Hex switch position
3 1 3 1
*
Attention!
Select always the shortest possible switching over tolerance enhancement of the valve position monitors
!
26
3
4
5
6
7
8
9
10
11
12
13
25
24
23
22
21
20
19
17
16
15
14
18
2
1
1
2
3
4
Hex-switches
FIESSLER
E L E K T R O N I K