Hydro Logger H1
User manual
36
electronics for ecology
FIEDLER
Con-
nection of terminals of galvanic isolator/breaker MIG485
SUITABLE TOPOLOGY
Connecting more than one measuring probe to the unit requires care to ensure
that the connection cable is pulled correctly. It is not advisable to connect a star-
shaped network, but due to the requirements for suppression of reflections, it
is advisable to connect the individual probes in series from the first to the last.
The following diagram shows the use of the MIG485 splitter to create two mu-
tually separated branches. Each branch can be grounded at one point without
balancing the currents through the ground loops due to galvanic isolation.
REST POTENTIALS OF TERMINALS A, B
The potentials of both RS485-A and RS485-B data lines must be voltage defined
on the master side. The wiring of the H1 register unit already contains circuitry
to define the quiescent state of the line: the RS485-A wire is held at a higher
potential than the RS485-B wire by internal resistors.
TERMINATING RESISTORS
Both ends of the RS485 network must be terminated with an impedance close
to the impedance of the cable used to suppress reflections. On the H1 unit side,
both RS485 serial lines are terminated with internal resistors.
In the case of a long line, it is advisable to strengthen this internal terminating
resistor on the H1 side with an additional external resistor of 150 to 330
Ω
loca-
ted between the RS485-A and 485-B terminals. The other end of the RS485 line
should always be supplemented with a terminating resistor. A 220 Ω resistor is
connected between the RS485-A and RS485-B terminals.
Содержание H1
Страница 1: ...Small telemetry station for water applications H1 H2 Hydro Logger user manual version 1 10 ...
Страница 2: ...Hydro Logger H1 User manual 2 electronics for ecology FIEDLER ...
Страница 80: ...Hydro Logger H1 User manual 80 electronics for ecology FIEDLER Notes ...
Страница 81: ...Hydro Logger H1 User manual FIEDLER electronics for ecology 81 ...