5
Commissioning
82
Festo – GDCP-CMMS/D-FW-EN – 1404NH – English
5.1.6
Fieldbus address/MAC-ID configuration
The address/ID configuration is evaluated for each power ON procedure or controller reboot (FCT). The
address/MAC-ID can be configured via the DIL switches [S1.1…7].
Fieldbus
DIL switch
[S1.7]
[S1.6]
[S1.5]
[S1.4]
[S1.3]
[S1.2]
[S1.1]
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
2
6
= 64
2
5
= 32
2
4
= 16
2
3
= 8
2
2
= 4
2
1
= 2
2
0
= 1
CANOpen
CAN address: 1…127
X
X
X
X
X
X
X
DriveBus
CAN address: 2…13
–
–
–
X
X
X
X
PROFIBUS DP
Bus address: 3…126
1)
X
X
X
X
X
X
X
DeviceNet
MAC-ID: 0…63
–
X
X
X
X
X
X
RS485
Address: 0…127
X
X
X
X
X
X
X
Example: 57 =
(Switch position)
+ 0
(OFF)
+ 32
(ON)
+ 16
(ON)
+ 8
(ON)
+ 0
(OFF)
+ 0
(OFF)
+ 1
(ON)
1)
The addresses “0…2” in Profibus DP are assigned to defined interfaces (e.g.: Higher-order controller, etc.).
Tab. 5.2
Fieldbus address/MAC-ID configuration
Note the instructions for address/MAC-ID parameterisation of fieldbuses
Description “device profile FHPP”, GDCP-CMMS/D-C-HP-...
Description “device profile CiA 402”, GDCP-CMMS/D-C-CO-...