![Festo CMMD-AS series Скачать руководство пользователя страница 218](http://html1.mh-extra.com/html/festo/cmmd-as-series/cmmd-as-series_description_2283098218.webp)
A
Diagnostic messages
218
Festo – GDCP-CMMS/D-FW-EN – 1404NH – English
Error group 04
Temperature monitoring, electronics
No.
Code
Message
Reaction
04-0
4210h
Excess/low temperature of power electronics
configurable
Cause
Motor controller is overheated.
–
Motor controller overloaded?
–
Temperature display plausible?
Action
•
Check installation conditions, cooling through the housing
surface, integrated heat sink and back wall.
•
Check the drive layout (due to possible overloading in continu-
ous operation).
Error group 05
Internal power supply
No.
Code
Message
Reaction
05-0
5114h
5 V electronics supply fault
PS off
Cause
Monitoring of the internal power supply has recognised under-
voltage. This is either due to an internal defect or an overload/
short circuit caused by connected peripherals.
Action
•
Separate device from the entire peripheral equipment and
check whether the error is still present after reset. If so, an
internal defect is present
Repair by the manufacturer.
05-1
5115h
Error in 24 V supply
PS off
Cause
Monitoring of the internal power supply has recognised under-
voltage.
Action
•
Check 24 V logic supply.
•
Separate device from the entire peripheral equipment and
check whether the error is still present after reset. If so, an
internal defect is present
Repair by the manufacturer.
05-2
5116h
12 V electronics supply fault
PS off
Cause
CMMS-ST only:
Monitoring of the internal power supply has recognised under-
voltage. This is either due to an internal defect or an overload/
short circuit caused by connected peripherals.
Action
•
Separate device from the entire peripheral equipment and
check whether the error is still present after reset. If so, an
internal defect is present
Repair by the manufacturer.
05-2
8000h
Driver supply error/driver supply failed
PS off
Cause
Only CMMS-AS/CMMD-AS:
Error in the plausibility check of the driver supply (safe torque off )
Action
•
Separate device from the entire peripheral equipment and
check whether the error is still present after reset. If so, an
internal defect is present
Repair by the manufacturer.
Содержание CMMD-AS series