0: Opens DACT Options menu.
1: Opens Phone Line Options menu for Line 1.
2: Opens Phone Line Options menu for Line 2.
3: Opens Account Options menu for Account 1.
4: Opens Account Options menu for Account 2.
1: Opens Communications Format menu Account n.
2: Opens Reporting Options menu for Account n.
3: Opens Account ID menu for Account n.
4: Opens Account CIC / Phone Number menu for Account n.
1: Selects reporting option for Alarms [Off, Can, Must].
2: Selects reporting option for Test [Off, Can, Must].
3: Selects reporting option for Troubles [Off, Can, Must].
4: Selects reporting option for Supervisory [Off, Can, Must].
# keys: enters account ID number for account n.
BKSP, <, > not operational.
Note: all 6 digits must be entered, with leading zeros if necessary.
# keys: enters CIC (dialing prefix) or phone number for account n.
<, >: moves backward or forward through numbers.
BKSP: Scrolls through special characters S (no digit), *, #, comma
(2 sec. Pause), and @ (dial Tone Select) without advancing cursor.
When desired character appears, press “>” to advance.
Note: Cursor is on first digit of phone # when menu opens.
1: Scrolls through Dialing Mode options for Line n [0...4].
0=USA Tone or rotary (40/60), 1=USA Rotary only, 2=Tone only,
3=Tone or European Rotary (33/67), 4=European Rotary only.
2: Toggles Line Monitoring ON/OFF for Line n.
Note: periodic line test is enabled when either line’s Line Monitor
setting is 1.
1: Scrolls through communication format options for Account n
[0...6]
0=SIA DCS 8, 1=SIA DCS 20, 2=Ademco Contact ID, 3=4/2
1400 HZ, 4=3/1 1400 HZ, 5=3/1 2300 HZ, 6=4/1 2300 HZ
1: Toggles DACT operation ON/OFF.
2: Toggles AC Fault reporting delay (0, 10, 20 hours).
3: Scrolls through number of line tests per day [1...4].
<, >: Scrolls First Line Test Time setting (15-minute steps).
[ACCTn] 000000
[ID # ] Type all 6 digits (leading 0s)
Main
Config
DACT
Account Options
Comm Format
[CONFG] 0:Options 1:Line1 2:Line2
[DACT] 3:Account1
4:Account 2
[ACCTn] 1:Format 2:Reporting
[OPTS ] 3:AccountID 4:CIC & Phone#
[ACCTn ] CIC:SSSSSSSS #:SSSSSSSSSSSSSSSS
[CIC, #] Type digits, BKSP/EDIT,
[LINEn] 1:Dialing Mode (0)
[OPTS ] 2:Line Monitor (ON)
[DACT] 1:DACT (OFF) :FirstTest 00:00
Config
[OPTS] 2:ACDelay (10)
3:Tests/day (1)
[ACCTn] 1:Alarms (Must) 2:Test (Can)
[REPRT] 3:Trbl (Can)
3:Spvsry (Off)
Main
Config
DACT
(opens only if DACT is installed)
Main
Config
DACT
Account Options
Main
Config
DACT
Account Options
Reporting Options
Main
Config
DACT
Account Options
Account ID Number
Main
Config
DACT
Account Options
CIC Number
- and -
Phone Number
[ACCTn] 1:Format (0)
[FORMT]
Main
Config
DACT
Line Options
Main
Config
DACT
Account Options
Comm Format
9000-0447
33 of 43
Technical Manuals Online! - http://www.tech-man.com
Содержание 7100 SERIES
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 7: ...9000 0447 5 of 43 Technical Manuals Online http www tech man com...
Страница 10: ...JMP1 BSM TB2 TB3 TB4 TB6 TB9 TB1 TB7 TB5 8 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 43: ...7100 Series Device Types and Functions 9000 0447 41 of 43 Technical Manuals Online http www tech man com...
Страница 44: ...Typical Wiring DRBC 1 to 7100 42 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...