Total
Total
Supv.
Alarm
Supv.
Alarm
Qty
Module
Description
Current
Current
Current
Current
BSM-1
Basic System Module, 1 SLC
0.056 A
0.076 A
BSM-2
Basic System Module, 2 SLC
0.065 A
0.085 A
BSM-1D
Basic System Module, 1 SLC
w/DACT
0.075 A
0.095 A
BSM-2D
Basic System Module, 2 SLC
w/DACT
0.085 A
0.105 A
AMM-2
Addressable Monitor
Module Style B
0.0002 A
0.0003 A
AMM-4
Addressable Monitor
Module
0.0002 A
0.005 A
AMM-4S
Addressable Monitor
Module
0.0002 A
0.005 A
AOM/
Addressable Output
AOM-2
Module
0.0002 A
0.005 A
ASD-P, PL,
PTL
Analog PE Sensor
0.0002 A
0.005 A
2551T
Analog PE Sensor w/therm.
0.0002 A
0.005 A
ASD-I, IL
Analog Ion Sensor
0.0002 A
0.005 A
ATD-L/
ATD-RL
Analog Thermal Sensor
0.0002 A
0.005 A
M500X
Fault Isolator Module
0.00025 A
0.00025 A
SPB-24
Projected beam smoke det.
0.00025 A
0.020 A
PTRM
Printer Transient Module
0.020 A
0.020 A
CAOM
Class A Option Module
0.001 A
0.001 A
MCOM
Municipal Circuit Option Module
0.001 A
0.001 A
LCD-7100 Optional Remote Serial Annunc.
0.050 A
0.075 A
Notification Appliances
Aux. Power Devices
Misc. devices
TOTALS
A
Total Supv. Current
B
Enter number of standby hours required**
C
Multiply Line A times hours in Line B—enter
D
Total alarm current from above
E
Enter alarm sounding period in hours. (5 minutes = .084 hr.)
F
Multiply Line D times Line E —enter
G
Total of Lines C & F—enter
H
Multiply Line G by 1.2 — enter (Total ampere/hours required*)
NOTE:
* Use next size battery with capacity greater than required. (Use only FCI Model B-1.9R, B-6R, B-7R,
B-17R, or B-31R batteries)
** 24 hrs for NFPA 72 protected premises or Central Station signaling, 60 hrs for Auxiliary or Remote
Supervising Station Fire alarm Systems. 90 hrs Factory Mutual standby requirement for deluge/preaction
systems with 15 minute alarm period.
See Page 43 for additional DRBC-1 connections when battery standby requirement exceeds 31 AH.
Table 2 Battery Standby Chart
9000-0447
15 of 43
Technical Manuals Online! - http://www.tech-man.com
Содержание 7100 SERIES
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 7: ...9000 0447 5 of 43 Technical Manuals Online http www tech man com...
Страница 10: ...JMP1 BSM TB2 TB3 TB4 TB6 TB9 TB1 TB7 TB5 8 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 43: ...7100 Series Device Types and Functions 9000 0447 41 of 43 Technical Manuals Online http www tech man com...
Страница 44: ...Typical Wiring DRBC 1 to 7100 42 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...