3.5 Analog Sensors
The 7100 accommodates only FCI approved, U.L. Listed, Factory Mutual Approved analog sensors and
bases. See FCI Publication, P/N 9000-0427 for a list of approved sensors and bases. Each signaling line circuit
can accommodate 99 sensor address points, using Address numbers 01 to 99.
3.5.1 Address Switches
Addresses are set via the rotary switches on each sensor or module. Setting the address is accomplished
by turning each of the two (2) rotary switches until they point to the numbers indicating the proper address (e.g.,
SW1 @ #2 and SW2 @ #5 would indicate address #25).
3.5.2 Drift Compensation
The 7100 contains a program which performs continuous testing of analog sensors, including sensitivity tests.
This program will compensate all analog sensors for age and environmental conditions. Should a problem occur
in a sensor, a “Failed Test”, “Dirty” or “Very Dirty” indication for the specific device will appear on the system
display and be recorded in the Event Log and the Serial Port.
3.6 Addressable Modules
The 7100 accommodates only FCI approved, U.L. Listed, Factory Mutual Approved addressable modules.
See FCI Publication, P/N 9000-0427 for a list of approved modules. Each SLC can accommodate 98 address-
able module points, using Addresses 101 through 198.
The modules that occupy this address range consist of Monitor (input) modules and Control (output) modules.
3.6.1 Address Switches
These addresses are set via the rotary switches on each module. Setting the address is accomplished by
turning each of the two (2) rotary switches until they point to the numbers indicating the proper address (e.g.,
SW1 @ #5 and SW2 @ #7 would indicate address # 157). Note that the “100" digit is pre-set in all addressable
modules.
3.7 Monitoring Modules
The 7100 accommodates only FCI approved, U.L. Listed, Factory Mutual Approved addressable monitor
modules. Dry contact devices and two wire smoke detectors can be monitored by these modules, which act
as the interface between the manual station, waterflow switch, etc. and the control panel.
See FCI Publication, P/N 9000-0427 for a list of approved modules.
3.8 Control Modules
The 7100 accommodates only FCI approved, U.L. Listed, Factory Mutual Approved addressable output
modules on its SLCs. See FCI Publication, P/N 9000-0427 for a list of approved modules.
Notification appliances, relays and circuits using compatible voltages (through an internal dry contact) can be
controlled by these modules.
3.9 Optional Modules
3.9.1 Class A Option Module (CAOM)
The CAOM provides Class A signaling for the notification appliance circuits and Class A, Style 6 signaling
for the signaling line circuits. It also provides a disconnect switch for each signaling line circuit and a common
disconnect switch for both notification appliance circuits. See Table 3 for wiring connections.
3.9.2 Municipal Circuit Option Module (MCOM)
The MCOM provides output for a Local Energy City Master Box, reverse polarity output for leased line
connection, or releasing solenoid output. See Table 3 for wiring connections and FCI Publication, P/N 9000-
0427 for a list of approved solenoids.
Ratings:
Master box (NPL)
Polarity Reversal (PL) Releasing Service (NPL)
Nominal voltage
24 VDC
24 VDC
24 VDC
Supervisory current
.0018 amp.
.012 amp.
.0005 amp.
Alarm current
.510 amp. (max.)
.012 amp.
.700 amp.
Line resistance
35 ohms (max.)
2 ohms (max.)
Trip coil resistance
14.5 ohms (max.)
IMPORTANT: In systems incorporating the Positive Alarm Sequence (PAS) in conjunction with addressable
modules, (AMM-2, -4, -4S), only one (1) initiating device may be connected to each module (address).
EXAMPLE: Connect only one manual station per AMM-2 module.
18 of 43
9000-0447
Technical Manuals Online! - http://www.tech-man.com
Содержание 7100 SERIES
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 7: ...9000 0447 5 of 43 Technical Manuals Online http www tech man com...
Страница 10: ...JMP1 BSM TB2 TB3 TB4 TB6 TB9 TB1 TB7 TB5 8 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 43: ...7100 Series Device Types and Functions 9000 0447 41 of 43 Technical Manuals Online http www tech man com...
Страница 44: ...Typical Wiring DRBC 1 to 7100 42 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...