2.0 Installation
2.1 General
The 7100 is shipped unassembled. The shipping carton contains an installation drawing, backbox, Basic
System Module (BSM), power transformer and door.
1) Refer to the System Assembly Drawing, P/N 9000-0457.
2) The BSM module consists of a main operating board with pluggable terminal strips, an 80-character LCD
display and programming keypad. Install this module immediately unless any option modules are to be used in
the system. The optional modules are supplied separately, and should be installed on the BSM before it is
mounted in the backbox. Before installing the BSM into the system backbox, refer to the installation instruction
sheets shipped with each module for the proper installation procedures.
3) Install the transformer into the backbox.
4) Install the door after the BSM is in place. Note that the door can only be installed (or removed) when it is
opened at least 90
o
from the backbox.
3.0 Basic System Module (BSM)
Designation Description
Comments
TB1-1
NAC Circuit 1 (+) Class B, Style Y
TB1-2
NAC Circuit 1 ( - ) Class B, Style Y
TB1-3
NAC Circuit 2 (+) Class B, Style Y
TB1-4
NAC Circuit 2 ( - ) Class B, Style Y
TB2-1
TRBL
Trouble contacts, N/O, 2 amp @ 30 VDC (resistive)
TB2-2
TRBL
Trouble contacts, Common
TB2-3
TRBL
Trouble contacts N/C
TB2-4
ALM
Alarm contacts, N/O, 2 amp. @ 30 VDC (resistive)
TB2-5
ALM
Alarm contacts, Common
TB2-6
ALM
Alarm contacts, N/C
TB2-7
Transfer control
TB2-8
Not used
TB3-1
Signaling Line Circuit 1 (+) Class B, Style 4
TB3-2
Signaling Line Circuit 1 ( - ) Class B, Style 4
TB3-3
Signaling Line Circuit 2 (+) Class B, Style 4 (7100-2, -2D only)
TB3-4
Signaling Line Circuit 2 ( - ) Class B, Style 4 (7100-2, -2D only)
TB4-1
Resettable Power, 24 VDC 1.0 amp.
TB4-2
Non-resettable Power, 24 VDC 1.0 amp.
TB4-3
System Common
TB4-4
Earth Ground
TB5-1
COM B
To LCD-7100 TB1-2
TB5-2
COM A
To LCD-7100 TB1-1
TB5-3, -4
Not used
TB6-1
AC “Hot”
120 VAC “Hot”, 50/60 Hz 2 amp., 240 VAC “Hot”, 50/60 Hz 1 amp.
TB6-2
Ground
Ground
TB6-3
AC Neutral
120 VAC Neutral, 240 VAC “Hot”
TB7-1
Batt+
Battery terminal (+)
TB7-2
Batt -
Battery terminal ( - )
TB9-1
DACT
Line 1 Tip In (non-power limited) From street
TB9-2
DACT
Line 1 Ring In (non-power limited) From street
TB9-3
DACT
Line 1 Tip Out (non-power limited) To phone
TB9-4
DACT
Line 1 Ring Out (non-power limited) To phone
TB9-5
DACT
Line 2 Tip In (non-power limited) From street
TB9-6
DACT
Line 2 Ring In (non-power limited) From street
TB9-7
DACT
Line 2 Tip Out (non-power limited) To phone
TB9-8
DACT
Line 2 Ring Out (non-power limited) To phone
Table 1 Field Wiring Connections
9000-0447
13 of 43
Technical Manuals Online! - http://www.tech-man.com
Содержание 7100 SERIES
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 7: ...9000 0447 5 of 43 Technical Manuals Online http www tech man com...
Страница 10: ...JMP1 BSM TB2 TB3 TB4 TB6 TB9 TB1 TB7 TB5 8 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 43: ...7100 Series Device Types and Functions 9000 0447 41 of 43 Technical Manuals Online http www tech man com...
Страница 44: ...Typical Wiring DRBC 1 to 7100 42 of 43 9000 0447 Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...