DRILL ON/OFF
SILENT TEST
AUDBL TEST
WALK / DRILL
I/O
OUTPUT ON/OFF
ENABLE/DISABLE
5.3 WALK / DRILL Menu Selection
Drill ON/OFF
Is a simple ON or OFF selection. ON will activate the NACs, while OFF will deactivate them.
Audible Test
Is a simple ON or OFF selection for an audible walk test. The NACs will sound twice for a
trouble, 3 times for a supervisory signal and 4 times for an alarm.
Silent Test Is a simple ON or OFF selection for a silent (no audible) walk test.
5.4 I/O Menu Selection
Output ON/OFF
forces the toggling on or off of a specified output. These outputs can include NAC 1,
NAC 2, Muni. Ckt. (if present) and any Addressable Control Point.
Enable/Disable
allows the user to take any addressable device on either SLC and disconnect it through
software. While disabled, a point will report a trouble until it is enabled, but will not cause or respond to an alarm.