DESCRIPTION
The System Sensor 2400 Series photoelectronic smoke de-
tectors are specifically designed to meet the performance re-
quirements of fire detection/alarm systems. These detectors
use state-of-the-art optical sensing chambers. The detectors
are designed to provide open area detection and are compati-
ble with FCI fire alarm control panels. The detectors’ opera-
tion and sensitivity can be tested in place. The Model 2400T
unit has the same specifications as the Model 2400, but in ad-
dition it features a built-in fixed temperature (135
o
F) thermal
detection unit.
Each detector has an LED which flashes every ten seconds
indicating that power is being applied to the detector. The
LED lights steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
The 2400 and 2400T detectors include a tamper-resistant
feature that, when used, prevents removal of the detector
without the use of a tool.
Sensitivity testing is performed either by inserting a tool
into the recessed test switch opening or inserting a calibrated
test card according to the test procedures.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and test kit MOD 400R.
APPROVALS
2400
SYSTEM SENSOR
PHOTOELECTRONIC
SMOKE DETECTOR
9020-0587/Ver. 1.0
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
FEATURES
·
Built-in Tamper-resistant Feature
·
Built-in Test Switch
·
Built-in Visual Alarm Indicator
·
Remote LED Option
·
Compatible with FCI Control Panels
·
Field Metering of Detector Sensitivity
·
Removable Insect Screen and Cover
for Field Cleaning
·
Sealed against Dirt, Insects, and Back
Pressure
·
Insect-resistant Screening
(.020"/.508mm openings)
·
Convenient Terminal Strip Wiring
TECHNICAL SPECIFICATIONS
Nominal sensitivity
3.0%/ft. obscuration
Operating voltage
8.5 - 35 VDC (24 VDC nominal)
Operating current
120 uA maximum
Operating temperature
32
o
to 120
o
F (0
o
to 49
o
C)
Operating humidity
10% to 93% relative humidity
Air velocity
3,000 fpm max.
Construction
Off-white flame-retardant plastic
Diameter
5.5 inches (14 cm)
Height
3.19 inches (8.0 cm) high,
Weight
0.7 lb. (310 gm)
NOTE: Alarm current is limited by control panel initiating device circuit.
ORDERING INFORMATION
Part Number
Model
Description
2400
Photoelectronic Detector
2400T
Photoelectronic Detector w/135
o
F thermal
An ISO 9001 Certified Company