![Fbt VAIE 2000 Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/fbt/vaie-2000/vaie-2000_manual_547128063.webp)
System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
3
VAC 2006 • VAR 2006
UK
2.2 VAR 2006 RoutER
F4. Failure-signalling LED.
F5. Router/system status LED.
F6. Output zone status LED.
F7.
Zone-selection buttons for BGM.
F8. Power supply/call status LED.
R1. ON/OFF switch.
R11. 2 relay outputs for signalling towards external peripheral units.
R12. Terminal block for 24 VDC outside power supply.
R13. Frame earth connection.
R14. Plug for 230 VAC mains power supply with built-in fuse.
R15. Terminal block for connection to amplifier outputs.
R16. Loudspeaker output terminal blocks
R17. Programmable inputs/outputs.
R18. Voice amplifier output -
Music/standby
amplifier output.
R19. Input/output for connection to a VAC 2006 controller.
2.1.1 Main features of the controller
• Monitored front-panel emergency microphone.
• Two-channel sound-broadcasting system.
• Message generator for broadcasting two-channel voice alarms (EVAC and ALERT).
• USB input as a source of background music.
• Automatic management of the stand-by amplifier.
• Input for 24 VDC secondary power supply.
• 7 programmable and controlled input contacts.
• 3 relay outputs.
• 6 control lines for digital amplifiers of the
dPu
range and/or
VAR 2006
routers and/or
VAIE 2250
integrated evacuation systems.
• 4 redundant lines for connections among the various different controllers (max 6).
• 2 redundant lines for emergency microphone bases of the
FMd
range (max 7, with 7 priority levels).
• 2 redundant lines for call stations of the
MBt
range (max 16, with 7 priority levels).
• B/W graphic display, 128x64 pixels, for easy configuration and rapid use of monitoring screen pages.
• Diagnostics and failure signalling.
• Can be mounted in a standard 19” rack (height: 2 units).
2.2.1 Main features of the router
• 6 two-line (A and B) loudspeaker zone outputs.
• 100-V double input for 1 or 2 voice amplifiers (IN 1: zones 1 to 3, IN 2: zones 4 to 6).
• 100-V input for music/standby amplifier.
• Music can be activated/de-activated separately for each zone by means of the front-panel push-buttons provided for this purpose.
• RJ45 sockets for connection to the
VAC 2006
controller.
• 7 programmable and controlled input contacts.
• 6 open-collector outputs.
• 2 relay outputs.
• Can be mounted in a standard 19” rack (height: 1 unit).