10
VAC 2006 • VAR 2006
UK
8.6.4
ALARM LEVEL
Adjustment of the volume of emergency sources
Panel for adjusting the output volume of emergency sources for the purpose of cali-
brating the system.
To adjust the volume of the required source:
• hold the corresponding numbered key (1 - 5) down.
and
• use the +/- knob to adjust the volume
Note: The volume set will be the same for all the output zones.
Upon completion, press ESC to return to the CONFIGURATION menu.
1-output volumes of the FMd emergency microphone stations connected to their local VAC 2006 unit:
the adjustment range for the EMERGENCY
UNITS is between -80 dB and 0 dB.
2-output volume of hand-held emergency microphones:
the adjustment range for FIRE MICROPHONES is between -80 dB and 0 dB.
It is suggested that in most cases a volume of +16 dB should not be exceeded.
3-output volume of pre-recorded ALERt messages:
the adjustment range for ALERT MESSAGES is between -80 dB and 0 dB.
4-output volume of pre-recorded EVACuAtIon messages:
The adjustment range for EVAC MESSAGES is between -80 dB e 0 dB.
5-Volume of emergency signals from VAC 2006 remote controllers:
the adjustment range for VAC 2006 LINk is between -80 dB e 0 dB.
8.6.6
PASSWoRd
Setting the password
Panel for enabling, disabling and customising the password for accessing the
system service levels.
• Use the +/- knob to position the cursor on each digit of the password to be
changed
• Use the numerical keys (1-6) to enter the new password
• Press Ok to enable or disable the password as set.
note:
The display will show the new password programming that has been set.
8.6.7
BEEP oPERAtIon
Management of the system “beep”
Panel for enabling and disabling the system “beep”.
• Use key
1
to enable or disable emission of the acoustic signal.
nota:
The display shows the status of the set programming.
Upon completion, press ESC to return to the CONFIGURATION menu.
8.6.5
AMPLIFIER tESt tIME
Setting the interval between test signals for testing amplifiers of the
dPu range
• Hold the corresponding numerical key (1 to 3) down and use the +/- knob to adjust
the setting:
1-Line Line
(1 to 6)
2-Amp Amplifier
(1 to 16 / ALL)
3-Time Length of test
(5s to 18h / no test)