![FBII XL-4 Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/fbii/xl-4/xl-4_programming-manual_3738648064.webp)
XL-4, XL-4B, and XL-5 LCD Keypad Programming Manual
Version 4
8–42
Relay 2 Select
122 RELAY 2 ATxx
NONE
Indicates the action taken for this alarm type on relay #2. If smoke reset verification function
is being utilized within the system then relay #2 will be dedicated to this application and the
relay type should be NONE.
Relay #2 can be used for purposes other than smoke detector reset if question 049 is disabled
and there are no zones programmed with a zone type specifying smoke detectors (question
143).
The options include:
NONE
PULSED
LATCHED
Press the 0 key to toggle between the available choices.
If desired both relays can be selected for a specific alarm type and the timeout selected will be
used for both relays.
UL
For UL Listed systems this option shall be programmed "NONE".
External Relay Address 1
123 XTRIG 1 ATxx
xx (00-40)
Selects a relay in the XL-4705 relay module for this alarm type. The number entered
represents the address as set on the dip switch in the XL-4705 relay module. (00 =Disable,
over 40 is invalid.)
External Relay Address 2
124 XTRIG 2 ATxx
xx (00-40)
Selects a relay in the XL-4705 relay module for this alarm type. The number entered
represents the address as set on the dip switch in the XL-4705 relay module. (00 =Disable,
over 40 is invalid.)
External Relay Address 3
125 XTRIG 3 ATxx
xx (00-40)
Selects a relay in the XL-4705 relay module for this alarm type. The number entered
represents the address as set on the dip switch in the XL-4705 relay module. (00 =Disable,
over 40 is invalid.)
Содержание XL-4
Страница 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...
Страница 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...
Страница 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...
Страница 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...
Страница 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...
Страница 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...
Страница 100: ...1 9 Al N9145V2 10 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset New York 11791 Copyright 1998 PITTWAY CORPORATION...